Logic Functions - Book 1

DIGITAL INPUT MODULE BLOCK (DIM)

5-3

5.2

DIGITAL INPUT MODULE BLOCK (DIM)

The digital input module block serves as the data handling block for the digital input module.
A digital input module conditions a field signal and processes the signal through an on-board
select circuit which passes all digital data between the modules and the module blocks at the
base scan rate of 50 milliseconds. Input filtering and power-up conditions are determined by
the digital input function block (DI). The digital input module block identifies a single point
connection to one of the following digital input modules:

DIM

2004A Solid State Relay Input
2006A Unconditioned Digital Input

Block outputs are the data, data quality, and active and unacknowledged status of the block’s
diagnostic error. A functional block diagram of a digital input module block is shown in Figure
5-2. The displays used to configure the Digital Input Module block are shown in Figures 5-3
and 5-4.

Manual

I/O

Selection

Unlock

Discrete Value

Auto

Mode

Input Module
• Solid State Relay Input
• Unconditioned Digital Input

I/O Mismatch

(SUPP/ENAB)

Auto

Manual

BAD

GOOD

Unlock

Lock

Error Check

I/O Lock

(from IF Block)

Lock

GOOD

Diagnostic

Group

(NONE, 1 - 7)

I/O Comm. Error

Field

Result

Result

Result

Quality

Board Number

Slot Number

MODMMA

MODMMU

MODMM

FRQ

1

2