Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual
Page 185
Logic Functions - Book 1
REMOTE I/O INTERFACE MODULE BLOCK
6-7
08
I/O Communication Error (BUSERRS) .............................................................................CWR
This diagnostic indicates that an error occurred in communication between the RIO module
and the instrument. This diagnostic can be suppressed or enabled as follows:
ENABLE
0
Diagnostic error is not suppressed and errors are reported to the
System Event block.
SUPPRESS
1
Diagnostic error is suppressed. Acknowledgement status remains
clear.
09
Unacknowledged I/O Communication Error (BUSERRU) ............................................. – WR
If the I/O communications error diagnostic is enabled, the unacknowledged diagnostic status
indicates if the diagnostic is or is not acknowledged. The status can be acknowledged or read
as follows.
NO
0
Diagnostic error is acknowledged.
YES
1
Diagnostic error is unacknowledged.
10
Active I/O Communication Error (BUSERRA) ................................................................ – WR
The active I/O communications error diagnostic status indicates if the error is active even after
acknowledgement. The status can be read as follows.
NO
0
Diagnostic error is not active.
YES
1
Diagnostic error is active.
11
Remote I/O Bus Communication Error (COMMERRS)...................................................CWR
This diagnostic indicates errors in communication or loss of communication between the RIO
interface module and the CS-31 bus. This diagnostic can be suppressed or enabled as
follows:
ENABLE
0
Diagnostic error is not suppressed and errors are reported to the
System Event block.
SUPPRESS
1
Diagnostic error is suppressed. Acknowledgement status remains
clear.
12
Unacknowledged Remote I/O Bus Communication Error (COMMERRU)................... – WR
If the remote I/O bus communications error diagnostic is enabled, the unacknowledged status
indicates if the diagnostic is or is not acknowledged. The status can be acknowledged or read
as follows.
NO
0
Diagnostic error is acknowledged.
YES
1
Diagnostic error is unacknowledged.
13
Active Remote I/O Bus Communication Error (COMMERRA) ...................................... – WR
If the remote I/O bus communications error diagnostic is enabled, the active status indicates if
the error is active even after acknowledgement. The status can be read as follows.
NO
0
Diagnostic error is not active.
YES
1
Diagnostic error is active.