Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual
Page 237
Logic Functions - Book 1
ANALOG INPUT BLOCKS (VCI, TII, TI, RI, RTI, RTTI)
7-27
VCI 20
Result Data Quality (RQ).................................................................................................. – WR
TTI 22
Result Data Quality (RQ).................................................................................................. – WR
TI 19
Result Data Quality (RQ).................................................................................................. – WR
RI 19
Result Data Quality (RQ).................................................................................................. – WR
RTI 9
Result Data Quality (RQ).................................................................................................. – WR
RTTI 22
Result Data Quality (RQ).................................................................................................. – WR
The quality attribute indicates quality of the input data. A bad quality is generated as a result
of conversion errors in the hardware, or if the converted value is over or under range.
GOOD
0
No conversion errors or over or under range conditions have been
reported.
BAD
1
The data quality field will go BAD if any of the blocks inputs becomes
bad while the block is in auto.
TI 20
Cold Junction Compensation Input (CJCINP) ................................................................CWR
The Cold Junction Compensation Input field is used for cold junction compensation if a local or
LSP floating point temperature input value is configured.
NONE
No local CJC input is applied. If the cold junction compensation field
in the connected TIM block is not NONE, it is used. Otherwise, both
fields are NONE, and no cold junction compensation takes place.
value
A floating point value in the units specified by the Temperature Scale
attribute (C, F, K, R).
LSP
A logical source pointer to a floating point value in the units specified
by the Temperature Scale attribute (C, F, K, R).
7.2.8
Typical Block Connections for Analog Input Type Block
Typical softwiring block structures used on softwiring diagrams are shown in Figure 7-19.
Softwiring connection to other
function block (result quality is
automatically connected).
ACTION
RQ
R
MODIN
Result Data Quality
Result
Operator write access to input
action and filter time.
Operator indication
of input action.
Action
Filter Time
VCIM1
MODOUT
CL11
I1
I2
VCI1
Figure 7-19. Typical Block Connections for Analog Input Type Block