Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual
Page 216
Logic Functions - Book 1
ANALOG INPUT BLOCKS (VCI, TII, TI, RI, RTI, RTTI)
7-6
Table 7-1. Voltage/Current Input Attributes, Valid Values, Mnemonics, and Data Types
Field Name /
Attribute
Mnemonic
Valid Values
CWR
Data Type
Attr
Version
VERSION
1
– – R Long State
00
Block Length
BLKLEN
– – R Count
01
State
STATE
RUN(0), HOLD(1), OFF(2),
DEBUG(3)
CWR Short State
02
Bad Inputs Accepted
BADINP
NO (0), YES (1)
CWR Discrete
03
Diagnostic Group Supp.
SUPPGRP
NONE, 1, 2, 3, 4, 5, 6, 7
CWR Long State
04
Calculation Error
CERRS
ENABLE (0), SUPPRESS (1)
CWR Discrete
05
Calc. Error Unacked
CERRU
NO (0), YES (1)
– WR Discrete
06
Calc. Error Unacked Quality
CERRUQ
NO (0), YES (1)
– WR Discrete
07
Calc. Error Active
CERRA
NO (0), YES (1)
– WR Discrete
08
Calc. Error Active Quality
CERRAQ
NO (0), YES (1)
– WR Discrete
09
Set quality bad on calc err?
SETQBAD
NO (0), YES (1)
CWR Discrete
10
Action
ACTION
REVERSE (0), DIRECT (1)
CWR Discrete
11
Linearization Type
LINTYPE
LINEAR(17), SQR(20),
SQRT(21), MOD_SQR(22),
MODSQRT(23)
CWR Long State
12
Filter Type
FILTYPE
NONE(0), AUTO(1), USER(2)
CWR Short State
13
Filter Time
FILTIME
0 to 1000 (minutes)
CWR Floating Pt
14
Output Range - Top
OUTHI
value (in scaled units)
CWR Floating Pt
15
Output Range - Bottom
OUTLO
value (in scaled units)
CWR Floating Pt
16
Quality Limit - Top
QUALHI
value (in scaled units)
CWR Floating Pt
17
Quality Limit - Bottom
QUALLO
value (in scaled units)
CWR Floating Pt
18
Initial Value (
Result)
R
value (in scaled units)
CWR Floating Pt
19
Result Data Quality
RQ
GOOD (0), BAD (1)
– WR Discrete