beautypg.com

Remote digital input module block (rdim) – Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual

Page 189

background image

Logic Functions - Book 1

REMOTE DIGITAL INPUT MODULE BLOCK (RDIM)

6-11

6.3

REMOTE DIGITAL INPUT MODULE BLOCK (RDIM)

The remote digital input module block is used to input as many as 16 digital inputs from a
remote digital input module connected to a CS-31 remote I/O network. The RDIM block is
valid for use with the following remote modules:

Module No.

Type

Description

ICSI 08 D1

Input

8 Non-isolated 24VDC input channels

ICSI 08 E1

Input

8 Isolated 24VDC input channels

ICSI 08 E3

Input

8 Isolated 120VDC input channels

ICSI 08 E4

Input

8 Isolated 230VDC input channels

ICSI 16 D1

Input

16 Non-isolated 24VDC input channels

ICSI 16 E1

Input

16 Isolated 24VDC input channels

ICSK 20 F1

Input/Output

12 non-isolated 24VDC input channels and 8
isolated relay output channels

ICSC 08 L1

Input/Output

8 user-configurable channels for 24VDC input
or 24VDC 500mA transistor output

The RDIM block receives the inputs from the CS-31 bus via a Remote I/O Interface (RIO)
Module installed in the instrument. The instrument database must have one RDIM block for
each remote digital input module on the CS-31 bus. The RDIM can be connected using the
RIO block MODOUT to this blocks MODIN connection.

Block outputs are the data, data quality, and active and unacknowledged status of the block’s
diagnostic error. A functional block diagram of an RDIM block is shown in Figure 6-4. Two of
the menus used to configure the block are shown in Figure 6-5 and Figure 6-6.