ICN Communication Block Capabilities

The ICN communication block is responsible for two main functions. The first is to handle all
messages received since its last execution. The second is to handle the reporting and
acknowledgment of diagnostics for the configured port. The ICN Block executes once every
50 msec. Messages received by the port driver are checked for proper reception and
definition. After passing those checks, the ICN Block’s responsibility is to route the message
so it may be processed at the appropriate time and by the appropriate process.

A write message follows these rules: If from a computer source, then source must be
authorized; if another source of the same type is in control, then it is NAK’d; if the source is in
control, the write is done and the control timer is reset; if there is no controlling source, only
the write is done.

4.2.2

ICN Communication Block Parameters

The mnemonics, valid values, and data types for all fields that may be selected for display
and/or be used in making softwiring connections are listed in Table 4-1. The following further
defines the ICN Communication Block configuration parameters.

Block Type
ICN

This is the Instrument Communication Block type and is configured on the I/O
Block Selection page.

Occurrence
1 to 3

There may be up to three ‘instances’ allowed of the ICN communication block.

Source 1 ............................................................................................................................. C – –
Source 2 ............................................................................................................................. C – –
Source 3 ............................................................................................................................. C – –
Source 4 ............................................................................................................................. C – –
Source 5 ............................................................................................................................. C – –
The source information provides the instrument with a complete source address of a computer
assigned to the instrument.

ANY

Entry made in Source 1 only. All computer sources are allowed.
Remaining source entries are ignored.

NONE

No authorized computer write source is defined. Computer status is
inactive.

ICN Addr

ICN Address switch setting (0 to 15) of ICN device (such as
MODCELL, SLU, or Communication Link)

Device Type

The device type must match what is written to the communications
link by the device. Communications source can be:

SLU

0....Sequence and Logic Unit

PC30

1....PC-30 Workstation

M300

2....MOD 300 System

1180M

4....1180M

MODCELL

5....MODCELL type instrument

Other

6....All device types

Will this module include a termination resistor?