beautypg.com

Analog input module block events, 8 analog input module block events – Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual

Page 166

background image

Logic Functions - Book 1

ANALOG INPUT MODULE BLOCKS (VCIM, TIM, RIM, WRIM)

5-46

VCIM 26

Field Result (FR) ............................................................................................................... – – R

TIM 24

Field Result (FR) ............................................................................................................... – – R

RIM 28

Field Result (FR) ............................................................................................................... – – R

WRIM 27

Field Result (FR) ............................................................................................................... – – R
This is the actual field input value to the instrument. A resistance input module count of
±25,000 is converted to the field result of 0 to 50,000.

VCIM 27

Field Result Quality (FRQ) ............................................................................................... – – R

TIM 25

Field Result Quality (FRQ) ............................................................................................... – – R

RIM 29

Field Result Quality (FRQ) ............................................................................................... – – R

WRIM 28

Field Result Quality (FRQ) ............................................................................................... – – R
The field result data quality will go bad if any of the blocks diagnostic errors becomes active.

5.4.7

Typical Block Connections for Analog Input Module Block

Typical softwiring block structures used on softwiring diagrams are shown in Figure 5-25.

Slot 1

Operator write access to set
mode and manual data.

Softwiring connection to
Voltage/Current Input Block (VCI).

MODE

RQ

R

VCIM1

Operator indication of
data quality and block
mode.

Result Quality

Mode

Field Result

1

2

TIM1

Field Result

RIM1

MODOUT

Slot 2

1

2

CJCIN

R

Result

Softwiring connection
to another block.

Result

Figure 5-25. Typical Block Connections for Analog Input Module Block

5.4.8

Analog Input Module Block Events

The event codes (and their suggested text messages) for the analog input module block types
are given below. See the referenced data base attributes (in brackets) for additional
information. See the system event block for a description of event transitions.

4

BLOCK MODE SET TO AUTO

5

BLOCK MODE SET TO MANUAL

6

I/O MISMATCH (5)

7

I/O COMMUNICATIONS ERROR (8)

8

VI MODULE ERROR (11)

or

8

TI MODULE ERROR (11)

or

8

RIM MODULE ERROR (11)

or

8

WRIM MODULE ERROR (11)