beautypg.com

5 - input/output module database parameters, Input/output module blocks, 5input/output module database parameters – Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual

Page 121

background image

Logic Functions - Book 1

INPUT/OUTPUT MODULE BLOCKS

5-1

5

INPUT/OUTPUT MODULE DATABASE PARAMETERS

5.1

INPUT/OUTPUT MODULE

BLOCKS

Input/Output module blocks define a physical input or output connection point and are not part
of a loop scan group. The I/O module blocks are available inside or outside of loop
compounds. One of these modules is required to get a field signal into the instrument. Local
I/O modules are selected from the Input/Output Library at the instrument or loop level. The
different types and their associated hardware modules are:

DIM

Digital Input Module. Reference

Section 5.2

. This block links MODOUT for

the following modules to a DI block (MODIN).
2004A Solid State Relay Input,
2006A Unconditioned Digital Input

DOM

Digital Output Module. Reference

Section 5.3

. This block has a discrete

attribute INPUT link for the following modules.
2005A Solid State Relay Output,
2007A Unconditioned Digital Output

WDOM

Wide Digital Output Module. Reference

Section 5.3

. This block has a discrete

attribute INPUT link for the following module.
2011A Mechanical Relay Output – Single Form C Type (two slots)

DDOM

Dual Digital Output Module. Reference

Section 5.3

. This block has two

discrete attribute INPUT links for the following module.
2011A Mechanical Relay Output – Dual SPST Type (two slots)

VCIM VCIM

Voltage/Current Input Module. Reference

Section 5.4

. This block links

MODOUT for the following modules to a VCI, TTI or RTTI block (MODIN).
2001A Voltage Input Module,
2002A Current Input Module,
2012A Current Input with 2-Wire Transmitter Power

TIM

TIM

Thermocouple Input Module. Reference

Section 5.4

. This block links

MODOUT for the following module to a TI block (MODIN).
2013A Thermocouple Input with Upscale Burnout Detection

RIM

RIM

Resistance Input Module. Reference

Section 5.4

. This block links

MODOUT for the following module to a RI or RTI block (MODIN) or a TIM
block (CJCIN).
2009A RTD Input (2 Wire)

WRIM WRIM

Wide Resistance Input Module. Reference

Section 5.4

. This block is

like RIM block except it links the following module.
2009A RTD Input (3 Wire)