Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual
Page 236
Logic Functions - Book 1
ANALOG INPUT BLOCKS (VCI, TII, TI, RI, RTI, RTTI)
7-26
TTI 16
Transmitter Range - Bottom (TRANSLO) ........................................................................ CWR
RTTI 16
Transmitter Range - Bottom (TRANSLO) ........................................................................ CWR
Transmitter bottom of range for TTI and RTTI blocks. Specified in result units as described for
Top of Range.
TTI 17
Output Calibrate - Zero (ZERO) ....................................................................................... CWR
TI 14
Output Calibrate - Zero (ZERO) ....................................................................................... CWR
RTI 14
Output Calibrate - Zero (ZERO) ....................................................................................... CWR
RTTI 17
Output Calibrate - Zero (ZERO) ....................................................................................... CWR
Zero calibration value for TTI, TI, RTI, and RTTI blocks. Specified in result units.
TTI 18
Output Calibrate - Span (SPAN)....................................................................................... CWR
TI 15
Output Calibrate - Span (SPAN)....................................................................................... CWR
RTI 15
Output Calibrate - Span (SPAN)....................................................................................... CWR
RTTI 18
Output Calibrate - Span (SPAN)....................................................................................... CWR
Span calibration value for TTI, TI, RTI, and RTTI blocks. Multiplier with 1.0 nominal.
VCI 17
Quality Limit - Top (QUALHI)............................................................................................ CWR
TTI 19
Quality Limit - Top (QUALHI)............................................................................................ CWR
TI 16
Quality Limit - Top (QUALHI)............................................................................................ CWR
RI 16
Quality Limit - Top (QUALHI)............................................................................................ CWR
RTI 16
Quality Limit - Top (QUALHI)............................................................................................ CWR
RTTI 19
Quality Limit - Top (QUALHI)............................................................................................ CWR
Sets result quality BAD if result exceeds this engineering units value. The top quality limit
must be greater than or equal to the bottom quality limit.
VCI 18
Quality Limit - Bottom (QUALLO) .................................................................................... CWR
TTI 20
Quality Limit - Bottom (QUALLO) .................................................................................... CWR
TI 17
Quality Limit - Bottom (QUALLO) .................................................................................... CWR
RI 17
Quality Limit - Bottom (QUALLO) .................................................................................... CWR
RTI 17
Quality Limit - Bottom (QUALLO) .................................................................................... CWR
RTTI 20
Quality Limit - Bottom (QUALLO) .................................................................................... CWR
Sets result quality BAD if result is less than this engineering units value. The bottom quality
limit must be less than or equal to the top quality limit.
VCI 19
Initial Value (Result) (R).................................................................................................... CWR
TTI 21
Initial Value (Result) (R).................................................................................................... CWR
TI 18
Initial Value (Result) (R).................................................................................................... CWR
RI 18
Initial Value (Result) (R).................................................................................................... CWR
RTI 18
Initial Value (Result) (R).................................................................................................... CWR
RTTI 21
Initial Value (Result) (R).................................................................................................... CWR
This is the output of the input block. This output is the result of an input module producing a
digital count of the analog signal and the input block filtering, normalizing, linearizing, and
converting the input count value to an engineering units value for VCI and RI blocks or to a
temperature value in the specified Temperature Scale units for TTI, TI, RTI, and RTTI blocks.