Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual
Page 258
Logic Functions - Book 1
APPENDIX B - MODBUS MASTER CONFIGURATION
B-14
INPUT7
REFRESH STATE
Local Long State
Support for the value of 255 was added in the release of Logic Controller
version 5 and Advanced Controller version 2.
IF REFRESH STATE = 0
Value 0 indicates the SEND INPUT is used and INPUT8 (SEND INPUT) must
be configured. The value 0 can only be written through the message handler
if the SEND INPUT is present.
ELSE IF REFRESH STATE = 255
If the SEND INPUT value is NONE or is TRUE, this message is sent to the
slave device.
ELSE IF REFRESH STATE = 1 through 254
This is how many times this block should execute before this message is sent
to the slave device. SEND INPUT value is not used.
INPUT8
SEND INPUT
LSP, Local Data or NONE Discrete
IF REFRESH STATE = 0
This input must be present. This signal is used to trigger this EX block’s
message. Signal is edge trigged, 0 (FALSE) to 1 (TRUE). Send input triggers
are ignored while this message transaction is ACTIVE.
ELSE IF REFRESH STATE = 255
If this value is NONE or is TRUE, this message is sent to the slave device.
ELSE IF REFRESH STATE = 1 through 254
This value is not used.
INPUT9
SLAVE ADDR
LSP or Local Data
Long State
Values can be 1 to 247.
INPUT10
STARTING REGISTER NUMBER
LSP or Local Data
Count
Values can be: 1 - 9999
Modbus function code 4
INPUT11 through INPUTn
Local Data
Any Data Type
except momentary discrete
This is where the data read from the slave device is stored.
INPUT11 will contain the value from the STARTING REGISTER NUMBER.
Depending on the data type the data may be contained in multiple registers.
See Modcell datatype to register mapping table above.