beautypg.com

Analog output module block parameters – Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual

Page 171

background image

Logic Functions - Book 1

ANALOG OUTPUT MODULE BLOCK (AOM)

5-51

5.5.2

Analog Output Module Block Parameters

The mnemonics, valid values, and data types for all fields that may be selected for display
and/or be used in making softwiring connections are listed in Table 5-10. The following further
defines the analog output module block configuration parameters.

Table 5-10. Analog Output Module Block Attributes, Valid Values, Mnemonics, and Data Types

Field Name /

Attribute

Mnemonic

Valid Values

CWR

Data Type

Attr

Version

VERSION

– – R Long State

00

Block Length

BLKLEN

– – R Count

01

State

STATE

RUN (0)

– – R Short State

02

Bad Inputs

BADINP

Rejected (0), Accepted (1)

CWR Discrete

03

Diagnostic Group

SUPPGRP

NONE, 1 to 7

CWR Long State

04

I/O Mismatch

MODMMS

ENABLE (0), SUPPRESS (1)

CWR Discrete

05

Unacked I/O Mismatch

MODMMU

NO (0), YES (1)

– WR Discrete

06

Active I/O Mismatch

MODMMA

NO (0), YES (1)

– – R Discrete

07

AO module comm. error

COMMERRS

ENABLE (0), SUPPRESS (1)

CWR Discrete

08

Unacked AO comm. Error

COMMERRU

NO (0), YES (1)

– WR Discrete

09

Active AO comm. Error

COMMERRA

NO (0), YES (1)

– – R Discrete

10

AO module Error

AOMERRS ENABLE (0), SUPPRESS (1)

CWR Discrete

11

Unacked AO module Error

AOMERRU NO (0), YES (1)

– WR Discrete

12

Active AO module Error

AOMERRA NO (0), YES (1)

– – R Discrete

13

I/O Mismatch

MODMM

FALSE (0), TRUE (1)

– – R Discrete

14

Board Number

BOARD

1

– – R Long State

15

Slot Number

SLOT

1 to 32

– – R Long State

16

Module ID

MODID

FD0500

– – R Hex

17

Extended Error

EXTERR

0 to 65535

– WR Count

18

Mode

MODE

MANUAL (0), AUTO (1)

CWR Discrete

19

Action

ACTION

REVERSE (0), DIRECT (1)

CWR Discrete

20

Input Range, Top

INHI

Floating Pt Value, E.U.

CWR Floating Pt

21

Input Range, Bottom

INLO

Floating Pt Value, E.U.

CWR Floating Pt

22

Output Range, Top

OUTHI

Floating Pt Value, Sig. Rng.

CWR Floating Pt

23

Output Range, Bottom

OUTLO

Floating Pt Value, Sig. Rng.

CWR Floating Pt

24

Output to use on restart

RESTART

PREVIOUS (0), PRESET (1)

CWR Discrete

25

Output to use on failsafe

FSACT

HOLD (0), PRESET (1)

CWR Discrete

26

Restart preset value

PRESET

Floating Pt Value, E.U.

CWR Floating Pt

27

Failsafe preset value

FSOUT

Floating Pt Value, E.U.

CWR Floating Pt

28

Track status

TRKSTAT

NO TRACK (0), TRACK (1)

– WR Discrete

29

Track status data quality

TRKQ

GOOD (0), BAD (1)

– WR Discrete

30

Scaled result

RSC

Floating Pt Value, E.U.

– WR Floating Pt

31

Scaled readback

RBSC

Floating Pt Value, E.U.

– – R Floating Pt

32

Local Input

INPUT

LSP or Floating Pt Value, E.U.

CWR Floating Pt

33

Readback

RB

Floating Pt Value, Sig. Rng.

– – R Floating Pt

34

Readback Quality

RBQ

GOOD (0), BAD (1)

– – R Discrete

35

Initial result

(Result)

R

Floating Pt Value, Sig. Rng.

C – R Floating Pt

36

Result Quality

RQ

GOOD (0), BAD (1)

– WR Discrete

37