Analog output module block parameters – Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual
Page 171
Logic Functions - Book 1
ANALOG OUTPUT MODULE BLOCK (AOM)
5-51
5.5.2
Analog Output Module Block Parameters
The mnemonics, valid values, and data types for all fields that may be selected for display
and/or be used in making softwiring connections are listed in Table 5-10. The following further
defines the analog output module block configuration parameters.
Table 5-10. Analog Output Module Block Attributes, Valid Values, Mnemonics, and Data Types
Field Name /
Attribute
Mnemonic
Valid Values
CWR
Data Type
Attr
Version
VERSION
– – R Long State
00
Block Length
BLKLEN
– – R Count
01
State
STATE
RUN (0)
– – R Short State
02
Bad Inputs
BADINP
Rejected (0), Accepted (1)
CWR Discrete
03
Diagnostic Group
SUPPGRP
NONE, 1 to 7
CWR Long State
04
I/O Mismatch
MODMMS
ENABLE (0), SUPPRESS (1)
CWR Discrete
05
Unacked I/O Mismatch
MODMMU
NO (0), YES (1)
– WR Discrete
06
Active I/O Mismatch
MODMMA
NO (0), YES (1)
– – R Discrete
07
AO module comm. error
COMMERRS
ENABLE (0), SUPPRESS (1)
CWR Discrete
08
Unacked AO comm. Error
COMMERRU
NO (0), YES (1)
– WR Discrete
09
Active AO comm. Error
COMMERRA
NO (0), YES (1)
– – R Discrete
10
AO module Error
AOMERRS ENABLE (0), SUPPRESS (1)
CWR Discrete
11
Unacked AO module Error
AOMERRU NO (0), YES (1)
– WR Discrete
12
Active AO module Error
AOMERRA NO (0), YES (1)
– – R Discrete
13
I/O Mismatch
MODMM
FALSE (0), TRUE (1)
– – R Discrete
14
Board Number
BOARD
1
– – R Long State
15
Slot Number
SLOT
1 to 32
– – R Long State
16
Module ID
MODID
FD0500
– – R Hex
17
Extended Error
EXTERR
0 to 65535
– WR Count
18
Mode
MODE
MANUAL (0), AUTO (1)
CWR Discrete
19
Action
ACTION
REVERSE (0), DIRECT (1)
CWR Discrete
20
Input Range, Top
INHI
Floating Pt Value, E.U.
CWR Floating Pt
21
Input Range, Bottom
INLO
Floating Pt Value, E.U.
CWR Floating Pt
22
Output Range, Top
OUTHI
Floating Pt Value, Sig. Rng.
CWR Floating Pt
23
Output Range, Bottom
OUTLO
Floating Pt Value, Sig. Rng.
CWR Floating Pt
24
Output to use on restart
RESTART
PREVIOUS (0), PRESET (1)
CWR Discrete
25
Output to use on failsafe
FSACT
HOLD (0), PRESET (1)
CWR Discrete
26
Restart preset value
PRESET
Floating Pt Value, E.U.
CWR Floating Pt
27
Failsafe preset value
FSOUT
Floating Pt Value, E.U.
CWR Floating Pt
28
Track status
TRKSTAT
NO TRACK (0), TRACK (1)
– WR Discrete
29
Track status data quality
TRKQ
GOOD (0), BAD (1)
– WR Discrete
30
Scaled result
RSC
Floating Pt Value, E.U.
– WR Floating Pt
31
Scaled readback
RBSC
Floating Pt Value, E.U.
– – R Floating Pt
32
Local Input
INPUT
LSP or Floating Pt Value, E.U.
CWR Floating Pt
33
Readback
RB
Floating Pt Value, Sig. Rng.
– – R Floating Pt
34
Readback Quality
RBQ
GOOD (0), BAD (1)
– – R Discrete
35
Initial result
(Result)
R
Floating Pt Value, Sig. Rng.
C – R Floating Pt
36
Result Quality
RQ
GOOD (0), BAD (1)
– WR Discrete
37