Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual
Page 152
Logic Functions - Book 1
ANALOG INPUT MODULE BLOCKS (VCIM, TIM, RIM, WRIM)
5-32
Table 5-6. Thermocouple Input Module Attributes, Valid Values, Mnemonics, and Data Types
Field Name /
Attribute
Mnemonic
Valid Values
CWR
Data Type
Attr
Version
VERSION
– – R Long State
00
Block Length
BLKLEN
– – R Count
01
Block State
STATE
RUN (0)
– – R Short State
02
Bad Inputs Accepted
BADINP
YES (1)
– – R Discrete
03
Diagnostic Group
SUPPGRP
NONE, 1 to 7
CWR Long State
04
I/O mismatch
MODMMS
ENABLE (0), SUPPRESS (1)
CWR Discrete
05
Unacked I/O Mismatch
MODMMU
NO (0), YES (1)
– WR Discrete
06
Active I/O Mismatch
MODMMA
NO (0), YES (1)
– WR Discrete
07
I/O communications error
COMMERRS
ENABLE (0), SUPPRESS (1)
CWR Discrete
08
Unacked comm. error
COMMERRU
NO (0), YES (1)
– WR Discrete
09
Active comm. error
COMMERRA
NO (0), YES (1)
– WR Discrete
10
TIM module error
TIMERRS
ENABLE (0), SUPPRESS (1)
CWR Discrete
11
Unacked Input Module Error
TIMERRU
NO (0), YES (1)
– WR Discrete
12
Active Input Module Error
TIMERRA
NO (0), YES (1)
– WR Discrete
13
I/O Module Mismatch
MODMM
FALSE (0), TRUE (1)
– – R Discrete
14
Board number
BOARD
1 through 8
– – R Long State
15
Slot number
SLOT
1 through 32
– – R Long State
16
Module id
MODID
FE0200
– – R Hex
17
Extended Error Code
EXTERR
0 to 65535
– WR Count
18
Mode
MODE
AUTO (1), MAN (0)
CWR Discrete
19
Thermocouple Type
TCTYPE
B (1), E (2), J (3), K (4), N (5),
R (6), S (7), T (8)
CWR Short State
20
Cold Junction Comp.
CJCLOC
NONE,
MODOUT connection from
RIM, WRIM, or value with suffix
of C, F, K, or R
CWR Floating Pt
21
Initial Result
(Result)
R
value
CWR Floating Pt
22
Result Quality
RQ
GOOD (0), BAD (1)
– WR Discrete
23
Field Result
FR
value
– – R Floating Pt
24
Field Result Quality
FRQ
GOOD (0), BAD (1)
– – R Discrete
25