INTERFACE BLOCK

3-27

196

Run completion cycles (RCCYCLES) ..............................................................................CWR
When leaving the RUN state, the instrument will wait up to ‘run completion cycles’ executions
(1 to 125) of the slowest user task for the run complete input to go TRUE. At that time it will
leave the run state regardless of the run complete input value.

197

Run complete input (RUNCMPLT) ...................................................................................CWR
Writable only if local data. When commanded to leave RUN, the instrument will wait (but only
up to ‘run completion cycles’ executions of the slowest user task) for this input to go TRUE
before changing states.

None

No run complete input. Instrument will change state when commanded.

TRUE

1

Local input TRUE causes instrument to leave RUN when commanded.

FALSE

0

Local input FALSE causes instrument to wait ‘x’ run completion cycles before
leaving RUN when commanded.

LSP

Logical source pointer determines TRUE or FALSE condition.

3.3.3

Typical Block Connections for Interface Block

Typical softwiring block structures used on softwiring diagrams are shown in Figure 3-5.

TIMEDAY

USRTAG

INSTATE

CMD

IF1

Command

Operator write access to change Tag and Time of Day

Logical Source Pointer to
another function block

Operator indication of
Instrument State, Tag, and
Time of Day

Logical Source Pointer from another
function block

Instrument State

User Tag

Time of Day

Figure 3-5. Interface Block, Typical Connections

3.3.3 Interface Block Events

The following event code errors (and their suggested text) must be acknowledged.
Informational events are not acknowledged. The order of values is not significant.

Event Codes (see referenced database attributes (in brackets) for descriptions)
4

DEFAULT DATABASE CHECKSUM ERROR (5)

5

MAIN DATABASE CHECKSUM ERROR (7)

6

INSTRUMENT IS UNCONFIGURED (9)

7

MAIN DATABASE VERSION ERROR (11)

8

MEMORY MODULE CHECKSUM ERROR (13)

9

MEMORY MODULE IS UNCONFIGURED (15)

10

MEMORY MODULE DATABASE VERSION ERROR (17)

11

MEMORY MODULE IS WRITE PROTECTED (20)

12

MEMORY MODULE IS SOFT WRITE PROTECTED (23)