Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual
Page 50
Logic Functions - Book 1
INTERFACE BLOCK
3-24
144
Calendar Date (DATE) .......................................................................................................– WR
A three byte value where the first byte is the calendar year (0 to 99), the second is the
calendar month (1 to 12) where 1 = January and 12 = December, and the third is the calendar
day (1 to 31). Note that years 90 to 99 are assumed to be 1990 to 1999.
145
Calendar Date Quality (DATEQ)....................................................................................... – – R
Quality byte for date attribute.
146
Day of Week (DAY) ............................................................................................................– WR
A short state value for the day of the week where 1 = Sunday and 7 = Saturday.
147
Day of Week Quality (DAYQ) ............................................................................................ – – R
Quality byte for day of week attribute.
Interface Block Status Attributes
148
Computer Status (CPSTATUS) ........................................................................................ – – R
Used to indicate computer status of controlling source for all overhead blocks.
Free
0
Indicates no computer has control.
Busy
1
Indicates some computer has control.
Inactive
2
Indicates no computer can get control, since there are no authorized
computer sources.
149
Console Status (CNSTATUS) ........................................................................................... – – R
Used to indicate console status of controlling source for all overhead blocks.
Free
0
Indicates no console has control.
Busy
1
Indicates some console has control.
Startup Conditions Attributes
150
Warm start duration (WARMSDUR) ................................................................................. CWR
A power-down/restart interval less than this will result in a warm start. Times less than 1
second are not useful because of potential drift between the battery backed and run time
clocks. If the clock chip is bad, the instrument will assume a power out time less than warm
start duration (unless warm start duration is NONE), and will begin timing at the power down
time. Valid values are:
NONE (zero)
INFINITY
Any time greater than 1 second
151
Cold start duration (COLDSDUR) .................................................................................... CWR
The cold start duration can be INFINITY or any power-down/restart time less than infinity and
greater than the warm start duration.
152
Run on mismatch (RUNMISMT) ....................................................................................... CWR
YES
1
The instrument does not stop in HOLD when an i/o mismatch is
detected in attempting to go to RUN. This can occur at power up
when the database or i/o is 'new', so that previous state doesn't
apply, or when the instrument is in the default or being configured
state and the user issues a run command.