Logic Functions - Book 1

DIGITAL INPUT MODULE BLOCK (DIM)

5-6

5.2.2

Digital Input Module Block Parameters

The mnemonics, valid values, and data types for all fields that may be selected for display
and/or be used in making softwiring connections are listed in Table 5-1. The following further
defines the Digital Input/Output Module Block configuration parameters.

Block Type
DIM

This is the Digital Input Module Block type.

Occurrence
1 to 32

There may be up to 32 ‘instances’ allowed of the DIM block type.

Table 5-1. Digital Input Module Block Attributes, Valid Values, Mnemonics, and Data Types

Field Name /

Attribute

Mnemonic Valid Values

CWR

Data Type

Attr

Version

VERSION

– – R Long State

00

Block Length

BLKLEN

– – R Count

01

Block State

STATE

RUN (0)

– – R Short State

02

Bad Inputs Accepted

BADINP

YES (1)

– – R Discrete

03

Diagnostic Group

SUPPGRP

NONE, 1 to 7

CWR Long State

04

I/O Mismatch

MODMMS

ENABLE (0), SUPPRESS (1)

CWR Discrete

05

Unacked I/O Mismatch

MODMMU

NO (0), YES (1)

– WR Discrete

06

Active I/O Mismatch

MODMMA

NO (0), YES (1)

– – R Discrete

07

I/O Module Mismatch

MODMM

0, 1

– – R Discrete

08

Board number

BOARD

1

– – R Long State

09

Slot number

SLOT

1 through 32

– – R Long State

10

Mode

MODE

MANUAL (0), AUTO (1)

CWR Discrete

11

Field Result

FR

FALSE (0), TRUE (1)

– – R Discrete

12

Field Result Quality

FRQ

GOOD (0) or BAD (1)

– – R Discrete

13

Initial Result Value

(Result)

R

FALSE (0), TRUE (1)

CWR Discrete

14

Result Quality

RQ

GOOD (0) or BAD (1)

– WR Discrete

15

02

Block State (STATE).......................................................................................................... – – R
Not configurable in this block (always equal to RUN). See Section 2.4.1, Block States for
additional information. This block, when configured, is always executed in the RUN state
(Normal Operation).

03

Bad Inputs Accepted (BADINP) ....................................................................................... – – R
This attribute is not used with this block. The DIM Module block always runs without a check
on input quality. See Section 2.3.2, Data Quality for additional information.

04

Diagnostic Group (SUPPGRP)......................................................................................... CWR
The diagnostic errors reported by this block can be grouped for System Event block control of
their reporting.

NONE

No group assigned.

1 to 7

Defines the diagnostic group number for the diagnostic suppression group

controlled by the System Event block.