Digital input module block parameters – Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual
Page 126
Logic Functions - Book 1
DIGITAL INPUT MODULE BLOCK (DIM)
5-6
5.2.2
Digital Input Module Block Parameters
The mnemonics, valid values, and data types for all fields that may be selected for display
and/or be used in making softwiring connections are listed in Table 5-1. The following further
defines the Digital Input/Output Module Block configuration parameters.
Block Type
DIM
This is the Digital Input Module Block type.
Occurrence
1 to 32
There may be up to 32 ‘instances’ allowed of the DIM block type.
Table 5-1. Digital Input Module Block Attributes, Valid Values, Mnemonics, and Data Types
Field Name /
Attribute
Mnemonic Valid Values
CWR
Data Type
Attr
Version
VERSION
– – R Long State
00
Block Length
BLKLEN
– – R Count
01
Block State
STATE
RUN (0)
– – R Short State
02
Bad Inputs Accepted
BADINP
YES (1)
– – R Discrete
03
Diagnostic Group
SUPPGRP
NONE, 1 to 7
CWR Long State
04
I/O Mismatch
MODMMS
ENABLE (0), SUPPRESS (1)
CWR Discrete
05
Unacked I/O Mismatch
MODMMU
NO (0), YES (1)
– WR Discrete
06
Active I/O Mismatch
MODMMA
NO (0), YES (1)
– – R Discrete
07
I/O Module Mismatch
MODMM
0, 1
– – R Discrete
08
Board number
BOARD
1
– – R Long State
09
Slot number
SLOT
1 through 32
– – R Long State
10
Mode
MODE
MANUAL (0), AUTO (1)
CWR Discrete
11
Field Result
FR
FALSE (0), TRUE (1)
– – R Discrete
12
Field Result Quality
FRQ
GOOD (0) or BAD (1)
– – R Discrete
13
Initial Result Value
(Result)
R
FALSE (0), TRUE (1)
CWR Discrete
14
Result Quality
RQ
GOOD (0) or BAD (1)
– WR Discrete
15
02
Block State (STATE).......................................................................................................... – – R
Not configurable in this block (always equal to RUN). See Section 2.4.1, Block States for
additional information. This block, when configured, is always executed in the RUN state
(Normal Operation).
03
Bad Inputs Accepted (BADINP) ....................................................................................... – – R
This attribute is not used with this block. The DIM Module block always runs without a check
on input quality. See Section 2.3.2, Data Quality for additional information.
04
Diagnostic Group (SUPPGRP)......................................................................................... CWR
The diagnostic errors reported by this block can be grouped for System Event block control of
their reporting.
NONE
No group assigned.
1 to 7
Defines the diagnostic group number for the diagnostic suppression group
controlled by the System Event block.