Remote digital output module block events – Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual
Page 210
Logic Functions - Book 1
REMOTE DIGITAL OUTPUT MODULE BLOCK (RDOM)
6-32
213,215...243
Result Quality,Channel 0 (R0Q) through Channel 15 (R15Q) ..........................................– WR
The result quality is set BAD when the input status is bad and bad inputs are not accepted, or
if the restart value cannot be read after a warm start. Any write to the result causes the result
quality to be set GOOD. The result quality is writeable in manual, when the I/O is locked, or
the instrument state is not run.
244
Packed Extended Errors (PKDERRS).............................................................................. – – R
Packed bits (channel 0 is LSB) indicating which channels have active extended errors. (The
last error reported since power-up is always preserved in EXTERR0-15, whether active or
not).
6.4.3
Typical Block Connections for Remote Digital Output Module Blocks
Typical RDOM block connections are shown in Figure 6-12. The application builder software
provides special connections to simplify the database configuration procedure required to
make data transfer connections between the remote digital output block and its associated
blocks. A single softwiring connection between the special MODOUT source and the special
MODIN destination provides for data transfer in a form that is acceptable to all of the
connected blocks.
LOLIM
HILIM
TM1
EXTERR0
MODE0
Input Value Channel 0 (I0)
Extended Error 0
Input Value Channel 1 (I1)
Input Value Channel 15 (I15)
MODIN
Mode Channel 0
RDOM1
MODOUT
RIO1
Low Limit
TS
Operator write access to set mode.
Operator indication of
attributes (through CL
block).
High Limit
PID1
Track Status
Figure 6-12. Remote Digital Output Module Block, Typical Connections
6.4.4
Remote Digital Output Module Block Events
The remote digital output module block event codes and their suggested run time display
messages are given below. See the referenced data base attributes (in brackets) for
additional information. See Section 3.4.5 for event transitions.
4
CHANNEL 0 MODE SET TO AUTO
5
CHANNEL 0 MODE SET TO MANUAL
•
•
•
34
CHANNEL 15 MODE SET TO AUTO
35
CHANNEL 15 MODE SET TO MANUAL
36
I/O MISMATCH (Attribute 05)
37
MODULE EXTENDED ERROR (Attribute 08)