Remote Digital Output Module Block Parameters

The mnemonics, valid values, and data types for all attributes that can be selected for display
and/or be used in making softwiring connections are listed in Table 6-3. A description of each
attribute is provided in the attribute list that follows the table.

Table 6-3. RDOM Block Attributes, Valid Values, Mnemonics, and Data Types

Field Name /

Attribute

Mnemonic Valid Values

CWR

Data Type

Attr

Version

VERSION

1

– – R

Long State

00

Block Length

BLKLEN

– – R

Count

01

State

STATE

RUN (0)

– – R

Short State

02

Bad Inputs Accepted

BADINP

NO(0)

– – R

Discrete

03

Diagnostic Group

SUPPGRP

NONE, 1, 2, 3, 4, 5, 6 or 7

CWR

Long State

04

I/O Mismatch

MODMMS

ENABLE(0), SUPPRESS(1)

CWR

Discrete

05

Unacked I/O Mismatch

MODMMU

NO(0), YES(1)

– WR

Discrete

06

Active I/O Mismatch

MODMMA

NO(0), YES(1)

– WR

Discrete

07

(Remote) Module Error

EXTERRS

ENABLE(0), SUPPRESS(1)

CWR

Discrete

08

Unacked Remote Module Error EXTERRU

NO(0), YES(1)

– WR

Discrete

09

Active Remote Module Error

EXTERRA

NO(0), YES(1)

– WR

Discrete

10

I/O Module Mismatch

MODMM

NO(0), YES(1)

– – R

Discrete

11

Slot number

SLOT

1 through 32

C – R

Long State

12

Remote I/O Bus Address

BUSADDR

1 to 31

C – R

Long State

13

Channel

INUSE

0 to 15

C – R

Count

14

Bad Inputs:

Channel 0 to

Channel 15

BADINP0
to
BADINP15

REJECTED(0), ACCEPTED(1) CWR

Discrete

15
to
30

Extended Error: Channel 0 to
Channel 15

EXTERR0
to
EXTERR15

0

No Error

Internal error in remote unit
Cut wire (open circuit)
Overload
Overload + open circuit
Short circuit
Short Circuit +open circuit
Overload + short circuit
Short circuit + overload + open
circuit
Remote unit not present
No remote I/O present

– WR

Long State

31
to
46

Mode:

Channel 0 to

Channel 15

MODE0
to
MODE15

MANUAL(0), AUTO(1)

CWR

Discrete

47
to
62

Action:

Channel 0 to

Channel 15

ACTION0
to
ACTION15

REVERSE(0), DIRECT(1)

CWR

Discrete

63
to
78

Restart Output

RSOUT0
to
RSOUT15

FALSE(0), TRUE(1)

CWR

Short State

79
to
94