Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual
Page 107
Logic Functions - Book 1
MODCELL SERIAL COMMUNICATION BLOCK
4-25
Table 4-2. Modcell Serial Communication Block Attributes, Valid Values, Mnemonics, and Data Types
Field Name /
Attribute
Mnemonic
Valid Values
CWR
Data Type
Attr
ModuleType
COMMTYPE
RS232 (0),
RS485 1 slot 2 wire (1)
RS232 with Address (5)
RS485 with Address (6)
C – R
Short State
80
Command
CMD
Reset Diag. Counters (1),
Initialize Serial Port (2)
Be a Master (251)
Be a Slave (252)
– WR
Long State
81
Reset Counters
RESET
NO (0), YES (1)
– WR
Discrete
82
Port Functionality
PORTFUNC
SLAVE (0), MASTER (1)
CWR
Short State
83
Target Address
TARADDR
ANY (0), 1 - 247
C – R
Long State
84
Use Default Comm
USEDEF
NO (0), YES (1)
– – R
Discrete
85
Write Message Timeout
WRTIMOUT
0 to 255
CWR
Long State
86
Write Message Action
WRACT
Discard (0), Process (1)
CWR
Short State
87
Foreground List
FG
NONE, CL10-CL4096
C – R
Count
88
05
Module missing or invalid (MODMMS) ............................................................................CWR
This diagnostic compares each slot configured for a MSC communications module against the
content of the slot during a power-up or database download. If the slot is empty or the
installed module does not match the configuration, this diagnostic is generated.
SUPPRESS
1
Diagnostic error is suppressed. Acknowledgement status remains
clear. Even though the I/O mismatch diagnostic is suppressed, the
actual I/O mismatch condition is still determined (see Attribute 30,
MODMM).
ENABLE
0
Diagnostic error is not suppressed and errors are reported to the
System Event block. The error message is reported as MODULE
MISMATCH.
06
Module Missing Unacked (MODMMU) ............................................................................ – WR
If the module missing or invalid diagnostic is enabled, this status indicates if the diagnostic is
or is not unacknowledged. The status can be acknowledged or read as follows.
NO
0
Diagnostic error is acknowledged.
YES
1
Diagnostic error is unacknowledged.
07
Module Missing Active (MODMMA)..................................................................................– – R
If the module missing or invalid diagnostic is enabled, this status indicates if the diagnostic is
or is not active. The status can be read as follows.
NO
0
Diagnostic error is not active.
YES
1
Diagnostic error is active.