Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual
Page 120
![background image](/manuals/337725/120/background.png)
Logic Functions - Book 1
MODCELL SERIAL COMMUNICATION BLOCK
4-38
MULTIPLE REGISTER READ/WRITE LIST 1
CL13
REGISTER
LSP
DATA TYPE
41001
EX3,I1
FLOAT PT
41003
EX3,I2
COUNT
41004
EX3,I3
MSEC TIME
41006
EX3,I4
DISCRETE
41007
EX3,I5
DATE
41009
EX3,I6
ASCII (SIZE 12)
41015
EX3,I7
LONG STATE
41016
EX3,I8
HEX (SIZE 9)
41021
EX3,I9
SHORT STATE
41022
EX3,I10
FLOAT PT
41024
EX3,I11
ASCII (SIZE 13)
41031
NONE
41032
NONE
MULTIPLE REGISTER READ/WRITE LIST 2
NO LIST SPECIFIED
MULTIPLE REGISTER READ/WRITE LIST 3
NO LIST SPECIFIED
MULTIPLE REGISTER READ/WRITE LIST 4
NO LIST SPECIFIED
MULTIPLE REGISTER READ/WRITE LIST 5
NO LIST SPECIFIED
MULTIPLE REGISTER READ ONLY LIST 1
CL14
REGISTER
LSP
DATA TYPE
31001
EX5,I1
FLOAT PT
31003
EX5,I2
COUNT
31004
EX5,I3
MSEC TIME
31006
EX5,I4
DISCRETE
31007
EX5,I5
DATE
31009
EX5,I6
ASCII (SIZE 12)
31015
EX5,I7
LONG STATE
31016
EX5,I8
HEX (SIZE 9)
31021
EX5,I9
SHORT STATE
31022
EX5,I10
FLOAT PT
31024
EX5,I11
COUNT
MULTIPLE REGISTER READ ONLY LIST 2
NO LIST SPECIFIED
MULTIPLE REGISTER READ ONLY LIST 3
NO LIST SPECIFIED
MULTIPLE REGISTER READ ONLY LIST 4
NO LIST SPECIFIED
MULTIPLE REGISTER READ ONLY LIST 5
NO LIST SPECIFIED
Occurrence number of
the configured list
specified in the MSC
Edit Block Display
(page 3) for Multiple
Register Read/Write
Memory, List 1.
Some data types use
more than one register
location. ASCII and Hex
data can use any
number of registers
depending on their field
size.
Occurrence number
of the configured list
specified in the MSC
Edit Block Display
(page 3) for Multiple
Register Read Only
Memory, List 1.
CLs specified in Multiple
Register Read/Write or Read
Only lists must be
configured and have a buffer
allocated. Nested lists are
not allowed.
ASCII data of field size
12 uses 6 registers.
Hex data of field size 9
uses 5 registers.
ASCII data of field size
13 uses 7 registers.