DIGITAL OUTPUT MODULE BLOCKS (DOM, DDOM, WDOM)
5-18
5.3.4
Digital Output Module Block Parameters
The following further defines the Digital Input/Output Module Block configuration parameters.
Block Type
DOM
This is the Digital Output Module Block type. It connects one 2005A
Solid State Relay Output or one 2007A Unconditioned Digital Output.
DDOM
This is the Dual Digital Output Module Block type. It connects one 2011A
Mechanical Relay Output (Dual SPST relay).
WDOM
This is the Wide Digital Output Module Block type. It connects one 2011A
Mechanical Relay Output (Single Form C relay).
Occurrence
1 to 32
There may be up to 32 ‘instances’ allowed of the digital output module
block types.
DOM 02
State (STATE) .................................................................................................................... – – R
DDOM 02
State (STATE) .................................................................................................................... – – R
WDOM 02
State (STATE) .................................................................................................................... – – R
Not configurable in this block (always equal to RUN). See Section 2.4.1, State Changes for
additional information. This block, when configured, is always executed in the RUN state
(Normal Operation).
DOM 03
Bad Inputs (BADINP)......................................................................................................... CWR
DDOM 03
Bad Inputs (BADINP1)....................................................................................................... CWR
DDOM 26
Bad Inputs (BADINP2)....................................................................................................... CWR
WDOM 03
Bad Inputs (BADINP)......................................................................................................... CWR
The digital output module blocks can run with a check on input quality. See Section 2.3.2,
Data Quality for additional information.
Accepted
1
Input data quality is not checked.
Rejected
0
Input data quality is checked. If input data quality is bad, the input will
not be used, the previous result will be sent to the output module, the
result quality will be marked BAD, and track status will be set to
TRACK.
DOM 04
Diagnostic Group (SUPPGRP)......................................................................................... CWR
DDOM 04
Diagnostic Group (SUPPGRP)......................................................................................... CWR
WDOM 04
Diagnostic Group (SUPPGRP)......................................................................................... CWR
The diagnostic errors reported by this block can be grouped for System Event block control of
their reporting.
NONE
No group assigned.
1 to 7
Defines the diagnostic group number for the diagnostic suppression group
controlled by the System Event block.