System event block parameters – Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual
Page 58
Logic Functions - Book 1
SYSTEM EVENT BLOCK
3-32
•
Example of events displayed by a user’s display (PC-30 device tag and header shown
for example only):
HH:MM:SS.mmm TAGxxxxx DDOM125 Remaining message = 47 characters total
DATE: Thu Apr 25/91
Device Block Transi-
TIME Tag /Occ. Event Code Message tion Msg
10:05:44.055 503TL ICN2 INVALID MESSAGE RECEIVED. uak-only
10:05:53.150 503TL ICN2 INVALID MESSAGE RECEIVED. acked
11:23:04.755 503TL IF1 INSTRUMENT BEING CONFIGURED.
11:23:12.410 503TL IF1 DOWNLOAD FROM SYSTEM.
11:24:49.237 503TL SE1 SYSTEM EVENT QUEUE CLEARED.
11:24:50.345 503TL IF1 INSTRUMENT IN RUN STATE.
15:03:25.673 503TL IC5 NOT RECEIVING DATA. act/uak
15:03:25.725 503TL IC23 NOT RECEIVING DATA. act/uak
15:03:25.763 503TL IC17 NOT RECEIVING DATA. act/uak
15:04:02.086 503TL SE1 ALL DIAGNOSTICS GLOBALLY ACKED.
15:04:02.130 503TL IC5 NOT RECEIVING DATA. acked
15:05:02.185 503TL IC23 NOT RECEIVING DATA. acked
15:05:02.238 503TL IC17 NOT RECEIVING DATA. acked
15:08:15.758 503TL IC5 NOT RECEIVING DATA. clr/ack
15:08:15.809 503TL IC23 NOT RECEIVING DATA. clr/ack
15:08:15.866 503TL IC17 NOT RECEIVING DATA. clr/ack
•
The system event queue is cleared when a database is downloaded from the PC
configurator and when a database is downloaded from a write protected memory
module.
•
The following Communication Link messages related to this block are supported by
the instrument:
READ EVENT QUEUE
READ DIAG STATUS
REFRESH DIAG STATUS
ALARM ACK
DIAGNOSTIC ACK
3.4.2 System Event Block Parameters
The mnemonics, valid values, and data types for all fields that may be selected for display
and/or be used in making softwiring connections are listed in Table 3-2. The following
further defines the System Event Block configuration parameters.
Block Type
SE
This is the System Event Block type and is always present on the Main
Block Selection page.
Occurrence
1
There is only one ‘instance’ allowed of the system event block.
02
State (STATE) ..............................................................................................................– – R
Not configurable in this block (always equal to RUN). This block is always executed
(normal operation). See Section 2.4.1, State Changes for additional information.
03
Bad Inputs (BADINP)...................................................................................................CWR
See Section 2.3.2, Data Quality for additional information.
ACCEPTED
1
The four acknowledge inputs are used without regards to quality.
REJECTED
0
Block checks data quality on its inputs and will only use the data
pointed at if the data quality is good.