Logic Functions - Book 1

REMOTE DIGITAL OUTPUT MODULE BLOCK (RDOM)

6-29

09

Unacknowledged Remote Module Error (EXTERRU).................................................... – WR
If this extended diagnostic error is enabled, the unacknowledged status indicates if the
diagnostic is or is not acknowledged. The status can be acknowledged or read as follows.

NO

0

Diagnostic error is acknowledged.

YES

1

Diagnostic error is unacknowledged.

10

Active Remote Module Error (EXTERRA)....................................................................... – WR
If this extended diagnostic error is enabled, the active status indicates if the error is active
even after acknowledgement. The status can be read as follows.

NO

0

Diagnostic error is not active.

YES

1

Diagnostic error is active.

11

I/O Module Mismatch (MODMM).......................................................................................– – R
Even though the I/O mismatch diagnostic may be suppressed and its value not stored with the
active I/O mismatch attribute, the actual I/O mismatch condition can still be determined by this
attribute (value is unsuppressed). This attribute is used to determine if there is an I/O
mismatch when changing the I/O mismatch diagnostic from suppressed to enabled.

NO

0

Diagnostic error is not active.

YES

1

Diagnostic error is active.

12

Slot Number (SLOT) ......................................................................................................... C – R
The slot (module location) number of the Remote I/O Interface Module to which this Remote
Digital Output block is connected. This number is assigned using the I/O Graphic in the
application builder program. Because the I/O interface module occupies two slots, the higher
numbered slot is always used.

13

Remote I/O Bus Address (BUSADDR) ............................................................................ C – R
The CS-31 Remote I/O Network address of the remote I/O module that provides the digital
outputs. Valid addresses are 1 through 31

14

Channel (INUSE) ............................................................................................................... C – R
This attribute is read as 16 bits indicating which channels are in use and thus represent active
digital outputs to the remote digital output module. Channel 0 is the least significant bit, and
the status of each channel is identified as follows:

NOT IN USE

0

Value when leaving the in use box blank for specific channel.

IN USE

1

Value when marking the in use box for specific channel.

15 - 30

Bad Inputs, Channel 0 (BADINP0) through Channel 15 (BADINP15) ...............................CWR
This block can run with a check on input quality. See Section 2.3.2, Data Quality for
additional information.

REJECTED

0

Input data quality is checked. If the quality is bad, the input is not
used, the previous result is sent to the output module, the result
quality is marked BAD, and track status is set to TRACK.

ACCEPTED

1

Input data quality is not checked.