Remote i/o interface module block parameters – Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual
Page 183
Logic Functions - Book 1
REMOTE I/O INTERFACE MODULE BLOCK
6-5
6.2.2
Remote I/O Interface Module Block Parameters
The mnemonics, valid values, and data types for all attributes that can be selected for display
and/or be used in making softwiring connections are listed in Table
6-1. A description of each
attribute is provided in the attribute list that follows the table.
Table 6-1
.
RIO Module Block Attributes, Valid Values, Mnemonics, and Data Types
Field Name /
Attribute
Mnemonic
Valid Values
CWR
Data Type
Attr
Version
VERSION
1
– – R
Long State
00
Block Length
BLKLEN
– – R
Count
01
State
STATE
RUN (0)
– – R
Short State
02
Bad Inputs Accepted
BADINP
YES(1)
– – R
Discrete
03
Diagnostic Group
SUPPGRP
NONE, 1, 2, 3, 4, 5, 6 or 7
CWR
Long State
04
I/O Mismatch
MODMMS
ENABLE(0), SUPPRESS(1)
CWR
Discrete
05
Unacked I/O Mismatch
MODMMU
NO(0), YES(1)
– WR
Discrete
06
Active I/O Mismatch
MODMMA
NO(0), YES(1)
– WR
Discrete
07
I/O Communication Error
BUSERRS
ENABLE(0), SUPPRESS(1)
CWR
Discrete
08
Unacknowledged I/O
Communication Error
BUSERRU
NO(0), YES(1)
– WR
Discrete
09
Active I/O Communication Error BUSERRA
NO(0), YES(1)
– WR
Discrete
10
Remote I/O Bus
Communication Error
COMMERRS
ENABLE(0), SUPPRESS(1)
CWR
Discrete
11
Unacknowledged Remote I/O
Bus Communication Error
COMMERRU
NO(0), YES(1)
– WR
Discrete
12
Active Remote I/O Bus
Communication Error
COMMERRA
NO(0), YES(1)
– WR
Discrete
13
Database Checksum Error
DBASERRS
ENABLE(0), SUPPRESS(1)
CWR
Discrete
14
Unacknowledged Database
Checksum Error
DBASERRU
NO(0), YES(1)
– WR
Discrete
15
Active Database Checksum
Error
DBASERRA
NO(0), YES(1)
– WR
Discrete
16
Module Error
EXTERRS
ENABLE(0), SUPPRESS(1)
CWR
Discrete
17
Unacknowledged Remote
Module Error
EXTERRU
NO(0), YES(1)
– WR
Discrete
18
Active Remote Module Error
EXTERRA
NO(0), YES(1)
– WR
Discrete
19
I/O Module Mismatch
MODMM
NO(0), YES(1)
– – R
Discrete
20
Slots
SLOT
1, 2, ... 31
C – R
Long State
21
Module Identification
MODID
FB0000
– – R
Hex
22
Extended Error
EXTERR
0
Not Supported
– WR
Long State
23
Bus Error Counter
BUSERRCT
– WR
Count
30