Remote I/O Interface Module Block Parameters

The mnemonics, valid values, and data types for all attributes that can be selected for display
and/or be used in making softwiring connections are listed in Table

6-1. A description of each

attribute is provided in the attribute list that follows the table.

Table 6-1

.

RIO Module Block Attributes, Valid Values, Mnemonics, and Data Types

Field Name /

Attribute

Mnemonic

Valid Values

CWR

Data Type

Attr

Version

VERSION

1

– – R

Long State

00

Block Length

BLKLEN

– – R

Count

01

State

STATE

RUN (0)

– – R

Short State

02

Bad Inputs Accepted

BADINP

YES(1)

– – R

Discrete

03

Diagnostic Group

SUPPGRP

NONE, 1, 2, 3, 4, 5, 6 or 7

CWR

Long State

04

I/O Mismatch

MODMMS

ENABLE(0), SUPPRESS(1)

CWR

Discrete

05

Unacked I/O Mismatch

MODMMU

NO(0), YES(1)

– WR

Discrete

06

Active I/O Mismatch

MODMMA

NO(0), YES(1)

– WR

Discrete

07

I/O Communication Error

BUSERRS

ENABLE(0), SUPPRESS(1)

CWR

Discrete

08

Unacknowledged I/O
Communication Error

BUSERRU

NO(0), YES(1)

– WR

Discrete

09

Active I/O Communication Error BUSERRA

NO(0), YES(1)

– WR

Discrete

10

Remote I/O Bus
Communication Error

COMMERRS

ENABLE(0), SUPPRESS(1)

CWR

Discrete

11

Unacknowledged Remote I/O
Bus Communication Error

COMMERRU

NO(0), YES(1)

– WR

Discrete

12

Active Remote I/O Bus
Communication Error

COMMERRA

NO(0), YES(1)

– WR

Discrete

13

Database Checksum Error

DBASERRS

ENABLE(0), SUPPRESS(1)

CWR

Discrete

14

Unacknowledged Database
Checksum Error

DBASERRU

NO(0), YES(1)

– WR

Discrete

15

Active Database Checksum
Error

DBASERRA

NO(0), YES(1)

– WR

Discrete

16

Module Error

EXTERRS

ENABLE(0), SUPPRESS(1)

CWR

Discrete

17

Unacknowledged Remote
Module Error

EXTERRU

NO(0), YES(1)

– WR

Discrete

18

Active Remote Module Error

EXTERRA

NO(0), YES(1)

– WR

Discrete

19

I/O Module Mismatch

MODMM

NO(0), YES(1)

– – R

Discrete

20

Slots

SLOT

1, 2, ... 31

C – R

Long State

21

Module Identification

MODID

FB0000

– – R

Hex

22

Extended Error

EXTERR

0

Not Supported

– WR

Long State

23

Bus Error Counter

BUSERRCT

– WR

Count

30