Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual
Page 137
Logic Functions - Book 1
DIGITAL OUTPUT MODULE BLOCKS (DOM, DDOM, WDOM)
5-17
Table 5-4. Wide Digital Output Module Block Attributes, Valid Values, Mnemonics, and Data Types
Field Name /
Attribute
Mnemonic
Valid Values
CWR
Data Type
Attr
Version
VERSION
1
– – R Long State
00
Block Length
BLKLEN
– – R Count
01
State
STATE
RUN (0)
– – R Short State
02
Bad Inputs
BADINP
Rejected (0), Accepted (1)
CWR Discrete
03
Diagnostic Group
SUPPGRP
NONE, 1 to 7
CWR Long State
04
I/O mismatch
MODMMS
ENABLE (0), SUPPRESS (1)
CWR Discrete
05
Unacked I/O Mismatch
MODMMU
NO (0), YES (1)
– WR Discrete
06
Active I/O Mismatch
MODMMA
NO (0), YES (1)
– – R Discrete
07
WDOM Module Error
WDOMERRS
ENABLE (0), SUPPRESS (1)
CWR Discrete
08
Unacked DO Module Error
WDOMERRU
NO (0), YES (1)
– WR Discrete
09
Active DO Module Error
WDOMERRA
NO (0), YES (1)
– – R Discrete
10
I/O Module Mismatch
MODMM
FALSE (0), TRUE (1)
– – R Discrete
11
Board Number
BOARD
1
– – R Long State
12
Slot Number
SLOT
1 to 32
– – R Long State
13
Action
ACTION
REVERSE (0), DIRECT (1)
CWR Discrete
14
Mode
MODE
MANUAL (0), AUTO (1)
CWR Discrete
15
Output to use on restart
RESTART
PREVIOUS (0), PRESET (1)
CWR Discrete
16
Preset Output Value
PRESET
FALSE (0), TRUE (1)
CWR Discrete
17
Failsafe Output Value
FSOUT
FALSE (0), TRUE (1),
FS HOLD (2)
CWR Short State
18
Track Status
TRKSTAT
NO TRACK (0), TRACK (1)
– WR Discrete
19
Track Status Quality
TRKQ
GOOD (0), BAD (1)
– WR Discrete
20
Initial Scaled Result Value
RSC
FALSE (0), TRUE (1)
CWR Discrete
21
Scaled Readback
RBSC
FALSE (0), TRUE (1)
– – R Discrete
22
Input
INPUT
LSP, FALSE (0), TRUE (1)
CWR Discrete
23
Readback
RB
FALSE (0), TRUE (1)
– – R Discrete
24
Readback Quality
RBQ
GOOD (0), BAD (1)
– – R Discrete
25
Result
R
FALSE (0), TRUE (1)
– – R Discrete
26
Result Quality
RQ
GOOD (0), BAD (1)
– WR Discrete
27