REMOTE DIGITAL OUTPUT MODULE BLOCK (RDOM)
6-28
03
Bad Inputs Accepted (BADINP) ....................................................................................... – – R
This attribute is present but is not used in this block. See attributes 15 through 30.
04
Diagnostic Group (SUPPGRP)......................................................................................... CWR
The diagnostic errors reported by this block can be grouped for System Event block control of
their reporting.
NONE
No group assigned.
1 to 7
Defines the diagnostic group number for the diagnostic suppression group
controlled by the System Event block.
05
I/O Mismatch (MODMMS) ................................................................................................. CWR
The I/O mismatch diagnostic compares each CS-31 bus address configured for a remote
digital I/O module against the content of the address during a power-up or data base
download. If the address is not used or the installed module does not match the configuration,
this diagnostic is generated.
SUPPRESS
1
Diagnostic error is suppressed. Acknowledgement status remains
clear. Even though the I/O mismatch diagnostic is suppressed, the
actual I/O mismatch condition is still determined (see Attribute 11,
MODMM).
ENABLE
0
Diagnostic error is not suppressed and errors are reported to the
System Event block. The error message is reported as I/O
MISMATCH
06
Unacknowledged I/O Mismatch (MODMMU)...................................................................– WR
If the I/O mismatch diagnostic error is enabled, the unacknowledged I/O mismatch diagnostic
status indicates if the diagnostic is or is not acknowledged. The status can be acknowledged
or read as follows.
NO
0
Diagnostic error is acknowledged.
YES
1
Diagnostic error is unacknowledged.
07
Active I/O Mismatch (MODMMA)......................................................................................– WR
If the I/O mismatch diagnostic error is enabled, the active I/O mismatch diagnostic status
indicates if the error is active even after acknowledgement. The status can be read as follows.
NO
0
Diagnostic error is not active.
YES
1
Diagnostic error is active.
08
Module Error (EXTERRS) ................................................................................................. CWR
This remote module error diagnostic checks for remote I/O module errors. Reported error
codes are stored in the block database as extended errors (EXTERR, attributes 31-46). The
diagnostic can be suppressed or enabled as follows:
ENABLE
0
Diagnostic error is not suppressed and errors are reported to the
System Event block.
SUPPRESS
1
Diagnostic error is suppressed. Acknowledgement status remains
clear.