APPENDIX A - VERSION DIFFERENCES
A-1
APPENDIX A
SUMMARY OF VERSION DIFFERENCES
A.1 GENERAL
This document is written to reflect the latest model and version of the instrument. The
summary provided below notes the differences between the current instrument and the
previous versions. Current functionality is: Logic 6, Advanced 3, MOD 30ML 2.
At present, upgrades are possible using the configurator. When an upgrade is done, any
blocks in the original database, which have later versions at the selected upgrade level, will be
upgraded to those later versions. This process will normally be irreversible, and the database
cannot be downgraded to its original level. A downgrade is possible if the database has only
those functions available in the earlier version.
The configurator tags each database it produces with the declared instrument version and the
minimum instrument version, which is the lowest instrument version capable of running the
database. The configurator determines, at the start of download, whether or not the target
instrument is capable of running the database and allows or disables the download
accordingly. The instrument itself makes a similar check when an attempt is made to
download from a memory module. The configurator will create a database based on the
declared instrument version when a database is uploaded.
A.2
LOGIC 5, ADVANCED 2, MOD 30ML 1 FUNCTIONALITY
These instrument versions do not include the following:
•
PW
Version 2 Piecewise support for attributes 4, 5, 6, 101 through 160 and 201
through 260. These attributes support tuneable X, Y values and recipe data
(table can be used as a data source other than linearization).
•
EX
Expression Block attributes 70 through 95, which add Inputs 21 through 46.
•
TOT
Totalizer Block
•
RSK
Ramp/Soak Block
•
PAD
Process Alarm Display Block, Version 2 supports a trip condition of DEVIATION.
A.3
LOGIC 4, REGULATORY 3, BATCH 1 FUNCTIONALITY
These instrument versions do not include the following remote I/O module blocks:
•
RIO
Remote I/O Interface Module Block
•
RDIM
Remote Digital Input Module Block
•
RDOM Remote Digital Output Module Block
In addition, the Version 1 Configured List Block does not support attributes 8, 9 and
10.