Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual
Page 52

Logic Functions - Book 1
INTERFACE BLOCK
3-26
164
Scan 6 Interval (INT6)........................................................................................................ – – R
The Interface and System Event Block scan group interval is set at 50 milliseconds. This task
manages instrument states, services diagnostics and the event queue, services the I/O, and
provides self checking (checksums).
165
Scan 7 Interval (INT7)........................................................................................................ – – R
166
Scan 8 Interval (INT8)........................................................................................................ – – R
167
Scan 9 Interval (INT9)........................................................................................................ – – R
ICN and Serial Communications Block 50 millisecond scan intervals for the communication
ports in the order found in the database (one task per module).
168
Scan 1 Execution Time (XTIME1) .................................................................................... – – R
169
Scan 2 Execution Time (XTIME2) .................................................................................... – – R
170
Scan 3 Execution Time (XTIME3) .................................................................................... – – R
171
Scan 4 Execution Time (XTIME4) .................................................................................... – – R
172
Scan 5 Execution Time (XTIME5) .................................................................................... – – R
173
Scan 6 Execution Time (XTIME6) .................................................................................... – – R
174
Scan 7 Execution Time (XTIME7) .................................................................................... – – R
175
Scan 8 Execution Time (XTIME8) .................................................................................... – – R
176
Scan 9 Execution Time (XTIME9) .................................................................................... – – R
Recent msec scan time for the associated scan group. This value is the number of
milliseconds of processor time used by each task in its most recent execution.
177
Scan 1 Filtered Execution Time (FTIME1)....................................................................... – – R
178
Scan 2 Filtered Execution Time (FTIME2)....................................................................... – – R
179
Scan 3 Filtered Execution Time (FTIME3)....................................................................... – – R
180
Scan 4 Filtered Execution Time (FTIME4)....................................................................... – – R
181
Scan 5 Filtered Execution Time (FTIME5)....................................................................... – – R
182
Scan 6 Filtered Execution Time (FTIME6)....................................................................... – – R
183
Scan 7 Filtered Execution Time (FTIME7)....................................................................... – – R
184
Scan 8 Filtered Execution Time (FTIME8)....................................................................... – – R
185
Scan 9 Filtered Execution Time (FTIME9)....................................................................... – – R
Average msec scan time for the associated scan group (updates after group executes).
186
Scan 1 Maximum Execution Time (MTIME1) ..................................................................– WR
187
Scan 2 Maximum Execution Time (MTIME2) ..................................................................– WR
188
Scan 3 Maximum Execution Time (MTIME3) ..................................................................– WR
189
Scan 4 Maximum Execution Time (MTIME4) ..................................................................– WR
190
Scan 5 Maximum Execution Time (MTIME5) ..................................................................– WR
191
Scan 6 Maximum Execution Time (MTIME6) ..................................................................– WR
192
Scan 7 Maximum Execution Time (MTIME7) ..................................................................– WR
193
Scan 8 Maximum Execution Time (MTIME8) ..................................................................– WR
194
Scan 9 Maximum Execution Time (MTIME9) ..................................................................– WR
Maximum msec scan time for the associated scan group since entering the current instrument
state. Value can be reset by writing any value to it.
195
Lock I/O blocks? (IOLOCK) .............................................................................................. CWR
If YES, output function block values will not be copied to the output module block output value,
and input module block values will not be copied to the input function blocks. Field input
values will continue to be updated in the input module blocks and output module block values
can be written to by the operator.