Logic Functions - Book 1

INTERFACE BLOCK

3-26

164

Scan 6 Interval (INT6)........................................................................................................ – – R
The Interface and System Event Block scan group interval is set at 50 milliseconds. This task
manages instrument states, services diagnostics and the event queue, services the I/O, and
provides self checking (checksums).

165

Scan 7 Interval (INT7)........................................................................................................ – – R

166

Scan 8 Interval (INT8)........................................................................................................ – – R

167

Scan 9 Interval (INT9)........................................................................................................ – – R
ICN and Serial Communications Block 50 millisecond scan intervals for the communication
ports in the order found in the database (one task per module).

168

Scan 1 Execution Time (XTIME1) .................................................................................... – – R

169

Scan 2 Execution Time (XTIME2) .................................................................................... – – R

170

Scan 3 Execution Time (XTIME3) .................................................................................... – – R

171

Scan 4 Execution Time (XTIME4) .................................................................................... – – R

172

Scan 5 Execution Time (XTIME5) .................................................................................... – – R

173

Scan 6 Execution Time (XTIME6) .................................................................................... – – R

174

Scan 7 Execution Time (XTIME7) .................................................................................... – – R

175

Scan 8 Execution Time (XTIME8) .................................................................................... – – R

176

Scan 9 Execution Time (XTIME9) .................................................................................... – – R
Recent msec scan time for the associated scan group. This value is the number of
milliseconds of processor time used by each task in its most recent execution.

177

Scan 1 Filtered Execution Time (FTIME1)....................................................................... – – R

178

Scan 2 Filtered Execution Time (FTIME2)....................................................................... – – R

179

Scan 3 Filtered Execution Time (FTIME3)....................................................................... – – R

180

Scan 4 Filtered Execution Time (FTIME4)....................................................................... – – R

181

Scan 5 Filtered Execution Time (FTIME5)....................................................................... – – R

182

Scan 6 Filtered Execution Time (FTIME6)....................................................................... – – R

183

Scan 7 Filtered Execution Time (FTIME7)....................................................................... – – R

184

Scan 8 Filtered Execution Time (FTIME8)....................................................................... – – R

185

Scan 9 Filtered Execution Time (FTIME9)....................................................................... – – R
Average msec scan time for the associated scan group (updates after group executes).

186

Scan 1 Maximum Execution Time (MTIME1) ..................................................................– WR

187

Scan 2 Maximum Execution Time (MTIME2) ..................................................................– WR

188

Scan 3 Maximum Execution Time (MTIME3) ..................................................................– WR

189

Scan 4 Maximum Execution Time (MTIME4) ..................................................................– WR

190

Scan 5 Maximum Execution Time (MTIME5) ..................................................................– WR

191

Scan 6 Maximum Execution Time (MTIME6) ..................................................................– WR

192

Scan 7 Maximum Execution Time (MTIME7) ..................................................................– WR

193

Scan 8 Maximum Execution Time (MTIME8) ..................................................................– WR

194

Scan 9 Maximum Execution Time (MTIME9) ..................................................................– WR
Maximum msec scan time for the associated scan group since entering the current instrument
state. Value can be reset by writing any value to it.

195

Lock I/O blocks? (IOLOCK) .............................................................................................. CWR
If YES, output function block values will not be copied to the output module block output value,
and input module block values will not be copied to the input function blocks. Field input
values will continue to be updated in the input module blocks and output module block values
can be written to by the operator.