beautypg.com

Using the modcell serial communication block, 5 using the modcell serial communication block – Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual

Page 118

background image

Logic Functions - Book 1

MODCELL SERIAL COMMUNICATION BLOCK

4-36

4.3.5

Using the Modcell Serial Communication Block

A Modbus Reference File, similar to the following file, is created for each MSC block that
exists in the database. Notice that an entry of NONE within a list block uses one register
location (point) and that some data types in the Multiple Register Read/Write and Read only
lists use more than one register location.

MSC2

DISCRETE READ/WRITE LIST 1
CL10

POINT

LSP

DATA TYPE

00001

D0M1,RSC

DISCRETE

00002

NONE

00003

D0M3,RSC

DISCRETE

00004

D0M4,RSC

DISCRETE

00005

NONE

00006

NONE

00007

D0M7,RSC

DISCRETE

00008

D0M8,RSC

DISCRETE

00009

NONE

00010

NONE

DISCRETE READ/WRITE LIST 2
NO LIST SPECIFIED
DISCRETE READ/WRITE LIST 3
NO LIST SPECIFIED
DISCRETE READ/WRITE LIST 4
NO LIST SPECIFIED
DISCRETE READ/WRITE LIST 5
NO LIST SPECIFIED

DISCRETE READ ONLY LIST 1
CL11

POINT

LSP

DATA TYPE

10001

EX2,I1

DISCRETE

10002

EX2,I2

DISCRETE

10003

EX2,I3

DISCRETE

10004

EX2,I4

DISCRETE

10005

EX2,I5

DISCRETE

10006

EX2,I6

DISCRETE

10007

EX2,I7

DISCRETE

10008

EX2,I8

DISCRETE

10009

EX2,I9

DISCRETE

10010

EX2,I10

DISCRETE

10011

NONE

10012

NONE

DISCRETE READ ONLY LIST 2
NO LIST SPECIFIED
DISCRETE READ ONLY LIST 3
NO LIST SPECIFIED
DISCRETE READ ONLY LIST 4
NO LIST SPECIFIED
DISCRETE READ ONLY LIST 5
NO LIST SPECIFIED

Occurrence number of the
configured list specified in
the MSC Edit Block Display
(page 2) for Discrete
Read/Write Memory, List 1.

Listing of all LSPs that
were configured in the
specified CL, including
their data types and point
locations.

No CLs were specified for
Discrete Read/Write
Memory Lists 2 through 5.

Occurrence number of the
configured list specified in
the MSC Edit Block Display
(page 2) for Discrete Read
Only Memory, List 1.

Each entry of NONE in a
specified CL (or ML) uses
one point location
(register).

CLs specified in Discrete
Read/Write or Read Only lists
must be configured and have
a buffer allocated. Nested
lists are not allowed.

All LSPs in the specified CL