Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual
Page 142
Logic Functions - Book 1
DIGITAL OUTPUT MODULE BLOCKS (DOM, DDOM, WDOM)
5-22
DOM 20
Track Status Quality (TRKQ)............................................................................................– WR
DDOM 23
Track Status Quality (TRKQ1)..........................................................................................– WR
DDOM 33
Track Status Quality (TRKQ2)..........................................................................................– WR
WDOM 20
Track Status Quality (TRKQ)............................................................................................– WR
This data quality field is not changed by any internal logic and will always be GOOD unless
written otherwise.
DOM 21
Initial Scaled Result Value (RSC) .................................................................................... CWR
DDOM 24
Initial Scaled Result Value (RSC1) .................................................................................. CWR
DDOM 34
Initial Scaled Result Value (RSC2) .................................................................................. CWR
WDOM 21
Initial Scaled Result Value (RSC) .................................................................................... CWR
This is the scaled result of the block evaluation. The result is writeable when the block is in
manual, the I/O locked, or the instrument state is not run (as during download of the
configuration, which establishes the initial result value). Any write to the scaled result will
cause the result quality to be set GOOD.
FALSE
0
Result before action is applied is open.
TRUE
1
Result before action is applied is closed.
DOM 22
Scaled Readback (RB) ...................................................................................................... – – R
DDOM 25
Scaled Readback (RB1) .................................................................................................... – – R
DDOM 35
Scaled Readback (RB2) .................................................................................................... – – R
WDOM 22
Scaled Readback (RB) ...................................................................................................... – – R
The value sent to the output module is read back from the select circuit every base scan cycle,
action is applied, and the value is stored as the scaled readback value.
DOM 23
Input (INPUT) ..................................................................................................................... CWR
DDOM 36
Input 1 (INPUT1) ................................................................................................................ CWR
DDOM 37
Input 2 (INPUT2) ................................................................................................................ CWR
WDOM 23
Input (INPUT) ..................................................................................................................... CWR
This is the input to the block used to determine the output. The input can be local data or a
logical source pointer. When the input is local data, it can be written.
FALSE
0
Local input value is low.
TRUE
1
Local input value is high.
LSP
Local input is a discrete logical source pointer.
DOM 24
Readback (RB)................................................................................................................... – – R
DDOM 38
Readback (RB1)................................................................................................................. – – R
DDOM 42
Readback (RB2)................................................................................................................. – – R
WDOM 24
Readback (RB)................................................................................................................... – – R
The value sent to the output module is read back from the select circuit every base scan cycle
and the value is stored as the readback value.
DOM 25
Readback Quality (RBQ)................................................................................................... – – R
DDOM 39
Readback Quality (RBQ1)................................................................................................. – – R
DDOM 43
Readback Quality (RBQ2)................................................................................................. – – R
WDOM 25
Readback Quality (RBQ)................................................................................................... – – R
Readback quality is set BAD if a digital output module error occurs.