Logic Functions - Book 1

ANALOG INPUT BLOCKS (VCI, TII, TI, RI, RTI, RTTI)

7-7

7.2.2

Thermocouple Transmitter Input Block Description (TTI)

This block is used to input a thermocouple transmitter’s value and translate it to a scaled
temperature. It receives its input from a voltage/current module block only. A functional block
diagram of a thermocouple transmitter input block is shown in Figure 7-4. The menus used to
configure the block are shown in Figure 7-5 and 7-6.

The mnemonics, valid values, and data

types for all fields that may be selected for display and/or be used in making softwiring
connections are listed in Table 7-2. Section 7.2.8 further defines the input block configuration
parameters.

BAD

GOOD

Signal Range - Top

Signal Range - Bottom

Module Type

Thermocouple Type

Input Module
Floating Point Count

Action

(DIR/REV)

Bad Inputs

Accepted
(YES/NO)

Result Quality

Filter Time

(minutes)

Input Module

No.

State

(RUN, HOLD,

OFF, DEBUG)

Filter Type

NONE

AUTO

USER

Filter

Quality and

Error Check

Input Module Result Quality

Result

Quality Limit
- Bottom

Quality Limit
- Top

Range Check

Normalization

and

Linearization

Diagnostic

Group

(NONE, 1-7)

CERRU

CERRA

Set Quality

Bad on

Calculation

Error (Y/N)

Calculation

Error

(ENAB/SUPP)

RANKINE

CELSIUS

FAHRENHEIT

KELVIN

Temperature Scale

Transmitter

Range Bottom

Transmitter

Range Top

Output Calibrate

- Zero

Output Calibrate

- Span

Mult

Sum

CERRUQ

CERRAQ

Figure 7-4. Thermocouple Transmitter Input Block (TTI), Functional Block Diagram