beautypg.com

ABUS FU9001 Privest Wireless Alarm Base Set Installation User Manual

Page 38

background image

7-38

Parameter

Quick-Key Parameter

Default

Range

Zone termination

A wired zone is monitored using a weak electric current. The electric current is defined by
the resistor used. You can terminate a zone as follows:

• N/C: (= normally closed) a zone termination is not necessary. It is important to

use detectors that open the circuit in the event of an alarm.

• EOL: (= single resistor) a zone termination with a resistor (2.2kOhm / red, red,

red, gold) is required. It is important to use detectors that open the circuit in
the event of an alarm.

• DEOL: (= double resistor) a zone termination with two resistors (2.2kOhm /

red, red, red, gold) is required. One resistor is inserted parallel to the tamper
contact of the detector. It is important to use detectors that open the circuit in
the event of an alarm.

• N/O: (= normally open) a zone termination is not necessary. It is important to

use detectors whose circuit closes in the event of an alarm.

To see how to wire a detector, see page 5-18.

NOTE:

For more information, see the wiring notes at the beginning of these instructions.
Zone loop response

Under zone loop response, you program the time that the wired zone has to be open
(closed) before an alarm is triggered.

The following options are available:

1) Normal: 400 ms (milliseconds)

7) 2 hours

2) Long: 1 second

8) 2.5 hours

3) Fast: 10 ms (milliseconds)

9) 3 hours

4) 30 minutes

10) 3.5 hours

5) 1 hour

11) 4 hours

6 ) 1.5 hours

22

22

22

Zone Label

Under Zone label, you can define or edit a name up to 15 characters long for each zone.

Under Parameters, press

22

to access the zone label menu option. You see the

following on the display:

Press

to name Zone 01 or enter a different zone number. You see the following

on the display:

Edit the zone name as described on page 8-34.

This manual is related to the following products: