beautypg.com

Eq5 ac drive operations manual – HP Anab EQ5 User Manual

Page 97

background image

EQ5 AC Drive Operations Manual

_______________________________________________________________________

TECO – Westinghouse Motor Company Trouble Shooting Chart 91

(4) Overvoltage

Overvoltage

during acceleration

OU1

Overvoltage

running at constant speed

OU3

Overvoltage

during deceleration

OU2

Reduce the supply voltage

to less than the specified

upper limit.

NO

Is the power supply voltage within the specified value?

Is start mode(H09) activated and its start-mode?

YES

YES

YES

NO

NO

NO

NO

NO

NO

YES

NO

NO

NO

NO

YES

Can the deceleration time be prolonged?

Reduce.

NO

Does OU alarm activate

when acceleration

is completed?

NO

YES

YES

Prolong.

NO

Can the acceleration

time be prolonged?

NO

NO

Can the moment of load inertia be reduced?

NO

NO

YES

Is the braking device or DC brake function in use?

YES

YES

YES

YES

YES

NO

Is restart mode after momentary power failure or

operation switching between line and inverter?

Does OU activated when the load is suddenly removed?

YES

Consider using

a braking system

or DC brake function.

YES

Restart time(H13) is

set longer.

YES

Check the motor and /or

the terminal(U, V, W)

is shorted or ground fault.

Does the main circuit DC link circuit

voltage exceed the protection level?

Faulty inverter

or error due to noise.

Contact TWMC.

Inspect the braking method. Contact TWMC.

(5) Low voltage

NO

NO

YES

YES

Low voltage

LU

Reset and restart

operation.

Replace the faulty part

and repair the connection.

Is power transformer
capacity adequate?

Has a (momentary) power

failure occurred?

Faulty parts or loose

connection in the

power circuit?

NO

YES

Does LU activate when

the circuit breaker or

magnetic contactor is

switched on?

Is there a load requiring

a large starting current
within the same power

distribution group?

YES

NO

YES

Is the main circuit DC voltage

(between P-N) higher than

the detection level specified

in Section 6.1.1?

NO

NO

YES

YES

Modify power distribution system

to satisfy the specified value.

The inverter may be faulty.

Contact TWMC.

Is the power supply

voltage within the

specified value?

Faulty of inverter control

circuit or error due

to noise, etc.

Contact TWMC.

This manual is related to the following products: