Eq5 ac drive operations manual – HP Anab EQ5 User Manual
Page 97
EQ5 AC Drive Operations Manual
_______________________________________________________________________
TECO – Westinghouse Motor Company Trouble Shooting Chart 91
(4) Overvoltage
Overvoltage
during acceleration
OU1
Overvoltage
running at constant speed
OU3
Overvoltage
during deceleration
OU2
Reduce the supply voltage
to less than the specified
upper limit.
NO
Is the power supply voltage within the specified value?
Is start mode(H09) activated and its start-mode?
YES
YES
YES
NO
NO
NO
NO
NO
NO
YES
NO
NO
NO
NO
YES
Can the deceleration time be prolonged?
Reduce.
NO
Does OU alarm activate
when acceleration
is completed?
NO
YES
YES
Prolong.
NO
Can the acceleration
time be prolonged?
NO
NO
Can the moment of load inertia be reduced?
NO
NO
YES
Is the braking device or DC brake function in use?
YES
YES
YES
YES
YES
NO
Is restart mode after momentary power failure or
operation switching between line and inverter?
Does OU activated when the load is suddenly removed?
YES
Consider using
a braking system
or DC brake function.
YES
Restart time(H13) is
set longer.
YES
Check the motor and /or
the terminal(U, V, W)
is shorted or ground fault.
Does the main circuit DC link circuit
voltage exceed the protection level?
Faulty inverter
or error due to noise.
Contact TWMC.
Inspect the braking method. Contact TWMC.
(5) Low voltage
NO
NO
YES
YES
Low voltage
LU
Reset and restart
operation.
Replace the faulty part
and repair the connection.
Is power transformer
capacity adequate?
Has a (momentary) power
failure occurred?
Faulty parts or loose
connection in the
power circuit?
NO
YES
Does LU activate when
the circuit breaker or
magnetic contactor is
switched on?
Is there a load requiring
a large starting current
within the same power
distribution group?
YES
NO
YES
Is the main circuit DC voltage
(between P-N) higher than
the detection level specified
in Section 6.1.1?
NO
NO
YES
YES
Modify power distribution system
to satisfy the specified value.
The inverter may be faulty.
Contact TWMC.
Is the power supply
voltage within the
specified value?
Faulty of inverter control
circuit or error due
to noise, etc.
Contact TWMC.