______________________________________________________________________

TECO – Westinghouse Motor Company Initial Operation 26

4. Power down the inverter and following safety
precautions, connect the motor. Power-up the
drive and repeat steps 1-3 and check the
following.
a. Is the direction of rotation correct?

b. Is the motor rotating smoothly with no
buzzing or abnormal vibration ?

Table 3-2-1 General Methods of Operation

Operation

mode

Frequency

setting

Operation
command

Operation
using
keypad

Keys on digital
operator

Operation
using
external
signal
terminals

Switch
contact input
Terminals:
FWD-CM
and
REV-CM

Freq. setting
Pot (VR),
analog
voltage,
analog current.

c. Is the acceleration and deceleration smooth?

5. If no abnormalities are detected, increase the frequency and check the above items again.

If the results of the trial run are normal, proceed to start a formal run.

Note - If an error is detected in the above procedure immediately stop the operation and attempt to

determine the cause by referring to Chapter 7, Troubleshooting.

DANGER

Since voltage is still applied to the main circuit terminals (L1/R, L2/S, L3/T), and auxiliary

control power terminals (R0, T0) even when the output from the inverter is terminated, do not
touch the terminals. The large capacitor(s) in the inverter are still charged after the power is
turned off and do not discharge immediately. Before touching any electric circuit, confirm that
the charge lamp is off or a multimeter verifies that the voltage at the P-N terminals is below 25
VDC.