Eq5 ac drive operations manual – HP Anab EQ5 User Manual
Page 29
EQ5 AC Drive Operations Manual
______________________________________________________________________
TECO – Westinghouse Motor Company Terminal Tightening Torques & Wire Size 23
2-3-5 EQ5 Terminal Tightening Torque and Cable Size
Input Voltag
e
HP
Rating
(CT / VT)
Terminal Tightening Torque
Ib – in (Nm)
(Note 4)
Cable Size AWG
(Note 3)
L1/R,
L2/S,
L3/T, U,
V, W, P1
& P(+)
E (G)
DB
Circuit
P(+), N(-)
& DB
(Note 1
)
R0
&
T0
L1/R,
L2/S &
L3/T
U, V & W
DC
Reactor,
P1 &
P(+)
DB Cir.
P(+), N(-)
& DB
(Note 1)
R0
&
T0
230
VAC
0.25 / 0.25
10.6 (1.2)
10.6 (1.2)
-
16 16
-
0.5 / 0.5
1 / 1
2 / 2
20.8 (2.36)
20.8 (2.36)
10.6
(1.2)
14
3 / 3
14
14
5 / 5
10
5 / 7.5
31.0 (3.5)
31.0 (3.5)
8
7.5 / 10
6
10 / 15
51.3 ( 5.8)
4
15 / 20
3
20 / 25
2
25 / 30
30 / 30
1
30 / 40
119 (13.5)
4/0 1/0 2/0
10
40 / 50
10
50 / 60
239 (27)
119
(13.5)
119 (13.5)
Qty 2-1
3/0
4/0
60 / 75
Qty 2-2/0
4/0
Qty 2-1
75 / 100
Qty 2-3/0
Qty 2-1/0
Qty 2-2/0
8
100 / 120
425 (48)
239 (27)
Qty 2-2/0
Qty 2-3/0
Qty 2-4/0
6
125 / 150
Qty 2-4/0
Qty 2-4/0
Qty 2-250
4
460
VAC
0.5 / 0.5
10.6 (1.2)
10.6 (1.2)
-
16
16
-
1 / 1
2 / 2
20.8 (2.36)
20.8 (2.36)
10.6
(1.2)
14
3 / 3
5 / 5
14
14
-
5 / 7.5
31.0 (3.5)
31.0 (3.5)
12
7.5 / 10
10
10 / 15
51.3 ( 5.8)
15 / 20
8
20 / 25
6
25 / 30
30 / 30
4
30 / 40
119 (13.5)
2
3
3
10
40 / 50
1
2
2
50 / 60
51.3 ( 5.8)
2/0
2
1
60 / 75
3/0
2/0
2/0
75 / 100
239 (27)
119
(13.5)
2/0
4/0
4/0
100 / 125
239 (27)
3/0
4/0
Qty 2-1
10
125 / 150
119 (13.5)
Qty 2-1/0
Qty 2-1/0
Qty 2-1/0
8
150 / 200
Qty 2-1/0
Qty 2-2/0
Qty 2-3/0
200 / 250
425 (48)
239 (27)
Qty 2-3/0
Qty 2-3/0
Qty 2-4/0
6
250 / 300
Qty 2-4/0
Qt y2-250
Qty 2-300
4
300 / 350
Qty 2-250
Qty 2-300
Qty 2-350
350 / 400
(Note 2)
Qty 2-350
Qty 2-400
Qt y2-500
(Note 2)
350 / 450
Qty 2-500
Qty 2-500
Qt y2-700
400 / 500
Qty 2-350
Qty 2-400
Qty 2-500
450 / 600
Qty 2-500
Qty 2-500
Qty 2-700
500 / 700
Qty 2-600
Qty 2-600
Qty 2-800
600 / 800
Qty 2-700
Qty 2-750
Qty 2-1000
Notes 1 - Based on TWMC standard DB unit and DB resistor designs.
2 - Consult Factory.
3 - Wire size from NEC tables 310-16. Copper wire rated 60°C for 100 Amps or less, 75°C for over 100 Amps in 30°C
Ambient, and 1.25 x drive rated Amps.
4 - Control terminals tightening torque, 6.2 (0.7)