beautypg.com

Eq5 ac drive operations manual – HP Anab EQ5 User Manual

Page 29

background image


EQ5 AC Drive Operations Manual

______________________________________________________________________

TECO – Westinghouse Motor Company Terminal Tightening Torques & Wire Size 23

2-3-5 EQ5 Terminal Tightening Torque and Cable Size

Input Voltag

e

HP

Rating

(CT / VT)

Terminal Tightening Torque

Ib – in (Nm)

(Note 4)

Cable Size AWG

(Note 3)

L1/R,

L2/S,

L3/T, U,

V, W, P1

& P(+)

E (G)

DB

Circuit

P(+), N(-)

& DB

(Note 1

)

R0

&

T0

L1/R,

L2/S &

L3/T

U, V & W

DC

Reactor,

P1 &

P(+)

DB Cir.

P(+), N(-)

& DB

(Note 1)

R0

&

T0

230

VAC

0.25 / 0.25

10.6 (1.2)

10.6 (1.2)

-

16 16

-

0.5 / 0.5

1 / 1
2 / 2

20.8 (2.36)

20.8 (2.36)

10.6

(1.2)

14

3 / 3

14

14

5 / 5

10

5 / 7.5

31.0 (3.5)

31.0 (3.5)

8

7.5 / 10

6

10 / 15

51.3 ( 5.8)

4

15 / 20

3

20 / 25

2

25 / 30
30 / 30

1

30 / 40

119 (13.5)

4/0 1/0 2/0

10

40 / 50

10

50 / 60

239 (27)

119

(13.5)

119 (13.5)

Qty 2-1

3/0

4/0

60 / 75

Qty 2-2/0

4/0

Qty 2-1

75 / 100

Qty 2-3/0

Qty 2-1/0

Qty 2-2/0

8

100 / 120

425 (48)

239 (27)

Qty 2-2/0

Qty 2-3/0

Qty 2-4/0

6

125 / 150

Qty 2-4/0

Qty 2-4/0

Qty 2-250

4

460

VAC

0.5 / 0.5

10.6 (1.2)

10.6 (1.2)

-

16

16

-

1 / 1
2 / 2

20.8 (2.36)

20.8 (2.36)

10.6

(1.2)

14

3 / 3
5 / 5

14

14

-

5 / 7.5

31.0 (3.5)

31.0 (3.5)

12

7.5 / 10

10

10 / 15

51.3 ( 5.8)

15 / 20

8

20 / 25

6

25 / 30
30 / 30

4

30 / 40

119 (13.5)

2

3

3

10

40 / 50

1

2

2

50 / 60

51.3 ( 5.8)

2/0

2

1

60 / 75

3/0

2/0

2/0

75 / 100

239 (27)

119

(13.5)

2/0

4/0

4/0

100 / 125

239 (27)

3/0

4/0

Qty 2-1

10

125 / 150

119 (13.5)

Qty 2-1/0

Qty 2-1/0

Qty 2-1/0

8

150 / 200

Qty 2-1/0

Qty 2-2/0

Qty 2-3/0

200 / 250

425 (48)

239 (27)

Qty 2-3/0

Qty 2-3/0

Qty 2-4/0

6

250 / 300

Qty 2-4/0

Qt y2-250

Qty 2-300

4

300 / 350

Qty 2-250

Qty 2-300

Qty 2-350

350 / 400

(Note 2)

Qty 2-350

Qty 2-400

Qt y2-500

(Note 2)

350 / 450

Qty 2-500

Qty 2-500

Qt y2-700

400 / 500

Qty 2-350

Qty 2-400

Qty 2-500

450 / 600

Qty 2-500

Qty 2-500

Qty 2-700

500 / 700

Qty 2-600

Qty 2-600

Qty 2-800

600 / 800

Qty 2-700

Qty 2-750

Qty 2-1000

Notes 1 - Based on TWMC standard DB unit and DB resistor designs.

2 - Consult Factory.

3 - Wire size from NEC tables 310-16. Copper wire rated 60°C for 100 Amps or less, 75°C for over 100 Amps in 30°C

Ambient, and 1.25 x drive rated Amps.
4 - Control terminals tightening torque, 6.2 (0.7)