EQ5 AC Drive Operations Manual

_______________________________________________________________________

TECO – Westinghouse Motor Company Serial Communications Modbus 113

8-4-5 Inverter Function Code Access

All of the inverter function codes are accessible through the RS-485 serial interface. Inverter
function codes are mapped to RTU holding registers. An inverter function code RTU address is
2 bytes in length. The high byte corresponds to a code that represents the inverter parameter
sort (F–M). The low byte corresponds to the inverter parameter number within the sort (0 -99).

high byte

low byte

inverter parameter sort code

inverter parameter number

Code

Sort

Name

Code

Sort

Name

0

F

Basic function

5

A

Motor 2 function

1

E

Terminal function

6

o

Option function

2

C

Control function

7

S

Command/function data

3

P

Motor 1 function

8

M

Monitor data

4

H

High level function

For example, inverter function code M11 the output current, is addressed as RTU parameter
number 080B hexadecimal or 2059 decimal.

8-4-6 Command and Monitor Data Registers

The command and monitor function codes are used to control the operation of the inverter and
monitor the status variables through the serial interface. The command and monitor function
codes are not accessible from the inverter keypad interface. Inverter parameter H30 and digital
input signal LE must be enabled to operate the inverter from the Modbus interface. If LE is not
assigned to a digital input (X1-X9), the signal will default to ON.


Frequency Setting Registers:

Address Code

Name

Unit

Variable Range

Min.

Unit

Read/

Write

Data

Format

1793 S01

Frequency

command

- -20000–20000

(max.

frequency at ± 20000)

1 R/W 2

1797 S05

Frequency

command

Hz 0.00–120.00

0.01 R/W

5

Notes: 1) If both S01 and S05 are set, the inverter will ignore the setting of S05.
2) A data setting that exceeds the setting range is possible, but the actual action will be limited
by the inverter configuration.


Operation command data Registers:

Address

Code

Name

Unit

Variable Range

Min.

Unit

Read/

Write

Data

Format

1798 S06

Operation

command

-

Refer to the data format [14]

- R/W 14

1799 S07

Universal

Do

-

Refer to the data format [15]

- R/W 15

1804 S12

Universal

Ao

-

-20000–20000 (100% output
at ± 20000 )

1 R/W 2

Notes: 1) Since X1–X9 are configurable input commands, it is necessary to set the functions by
E01–E09.

2)The alarm reset is executed, when RST signal changes from ON to OFF even if there are no

alarms.

3) Universal Do is a function that utilizes the inverter’s digital outputs via communication.