beautypg.com

HP Anab EQ5 User Manual

Page 69

background image

TECO

–Westinghouse Motor Company Function Explanation 63

This function outputs an inverted signal to Running
(RUN) to indicate zero speed. An ON signal is output
when the DC injection brake function is operating.

This function outputs an ON signal when the inverter is
ready to operate. The inverter is ready to operate when
the main circuit and control circuit power is established
and the inverter protective function is not activating.
About one second is required from power-on to ready for
operation in normal condition.


To perform switching operation between the line and the
inverter, the sequence prepared in the inverter can be
used to select and output signals for opening and closing
the magnetic contactors connected to the inverter. As
the operation is complex, refer to technical
documentation for the EQ5 series when using this
function.
As the sequence will operate automatically when SW88
or SW52-2 is selected, do not select when not using the
sequence.

When a signal for switching to motor 2 is input from the
terminal selected by terminals [X1] to [X9], this function
selects and outputs the signal for switching the magnetic
contactor for the motor. As this switching signal is not
output during running including when the DC injection
braking function is operating, a signal must be re-input
after output stops.

When an operation (forward or reverse) command is
entered, this function outputs an ON signal. When a
stop command is entered, the signal goes off after
inverter output stops. When a coast-to-stop command
is entered and the inverter protective function operates,
the signal goes off immediately.

When the pattern operation stage changes, this function
outputs a one-shot (100ms) ON signal to report a stage
change.

When the seven stages of a pattern operation are
completed, this function outputs a one-shot (100 ms) ON
signal to report the completion of all stages.

During pattern operation, this function reports the stage
(operation process) being operated.

Pattern operation

stage No.

Output terminal

STG1

STG2

STG4

Stage 1

on

off

off

Stage 2

off

on

off

Stage 3

on

on

off

Stage 4

off

off

on

Stage 5

on

off

on

Stage 6

off

on

on

Stage 7

on

on

on

When pattern operation is not activated (i.e., no stage is
selected), the terminals do not output a signal.

This function reports the operating status of the inverter
protective function.

Alarm detail

(inverter protective function)

Output terminal

AL1 AL2 AL4 AL8

Overcurrent, ground fault, fuse blown

on

off

off

off

Overvoltage

off

on

off

off

Undervoltage shortage, input phase failure

on on

off

off

Motors 1 and 2 overload

off

off

on

off

Inverter overload

on

off

on

off

Heat sink overheating, inverter inside overheating

off

on on

off

External alarm input, braking resistor overheating

on on on

off

Memory error, CPU error

off

off

off

on

Keypad panel communication error, option communication error

on

off

off

on

Option error

off

on

off

on

Output wiring error

off

off

on on

RS-485 communication error

on

off

on on

Not Used EQ5

off

on on on

In normal operation terminals do not output a signal.

When used with "H06 Cooling fan ON/OFF control," this
function outputs a signal while the cooling fan is
operating.

When a value of 1 or larger is set to "H04 Retry
operating," the signal is output while retry operation is
activating when the inverter protective function is
activated.

Assigning value "27" to a transistor output terminal
renders the terminal a universal DO terminal.
This function enables ON/OFF through the RS-485 and
BUS option.
This function serves only to turn on and off the transistor
output through communication and is not related to
inverter operation.

This function outputs a early warning signal when heat
sink temperature is (overheat detection level - 10℃) or
higher.


When either of data for the Life expectancy judgment

of the function code:U09 to U11 reaches at the Life
expectancy judgment level, the ON signal is output.
However, the inverter does not do alarm.
Moreover, the alarm output for any fault (30A, 30B,
30C ) does not operate.

Function

code

Parts of

Life expectancy judgment

Life expectancy

judgment level

U09

Capacitor in main circuit

85% or less of the initial value

U10

Electrolytic capacitor on PCB

61,000 hours

U11

Cooling fan

25,000 hours

U59

DC fan broken for stir internal
unit up
[40HP/CT, 50HP/VT or more is
annunciated.]

DC fan is broken

Inverter stopping [STOP]

Ready output [RDY]

Line/Inv changeover [SW88] [SW52-2] [SW52-1]

Auto-resetting [TRY]

Cycle completion signal for pattern operation [TO]

Motor 2 /Motor 1 [SWM2]


Auxiliary terminal [AX]


Time-up signal for pattern operation [TU]


Stage No. indication for pattern operation [STG1] [STG2] [STG4]

Alarm indication [AL1] [AL2] [AL4] [AL8]

Overheat early warning [OH]

Fan operation signal [FAN]

Universal DO [U-DO]

Life expectancy detection signal [LIFE]

This manual is related to the following products: