Eq5 ac drive operations manual, Specifications, 1 standard specifications – HP Anab EQ5 User Manual
Page 110: Eq5 ct (constant torque) – 230v series, Eq5 vt (variable torque) – 230v series
EQ5 AC Drive Operations Manual
_________________________________________________________________________
TECO – Westinghouse Motor Company Standard Specifications Notes con’t 10
4
8. Specifications
8-1 Standard Specifications
EQ5 CT (Constant Torque) – 230V Series
Type
NEMA 1
OPEN CHASSIS
Applied Motor
Nominal (HP)
0.25
0.5 1 2 3 5 5 7.5
10
15
20
25
30 30 40 50 60 75 100 125
Model
EQ5-2XXX-XX
0P2
-N1
0P5
-N1
001
-N1
002
-N1
003
-N1
005
-N1
007
-N1
010
-N1
015
-N1
020
-N1
025
-N1
030
-N1
032
-N1
040
-C
050
-C
060
-C
075
-C
100
-C
125
-C
150
-C
Rated output
capacity [kVA] (*1)
0.6 1.2 2.0 3.2 4.4 6.8 6.8 10 13 18 24 29 35 35 46 58 72 86 113 138
Rated output
current [A] (*2)
1.5 3.0 5.0 8.0 11 17 17 25 33 46 59 74 87 87 115 145 180 215 283 346
Overload
capability
150% of rated output current for 1 min.
200% of rated output current for 0.5 s
150% of rated output current for 1 min.
180% of rated output current for 0.5 s
Starting torque
200% or more (under torque vector control)
180% or more (under torque vector control)
Output
ratings
Rated output
voltage [V] (*3)
3-phase, 200V/50Hz, 200V,220V,230V/60Hz
Rated output
frequency [Hz]
50,60Hz
Input ratings
Phases, voltage,
frequency
3-phase, 200 to 230V, 50/60Hz
3-phase, 200 to 220V, 220 to 230V/50Hz
3-phase, 200 to 230V/60Hz
Voltage/frequency
variations
Voltage: +10% to -15% (Imbalance rate between phases: 2% or less (*5) , Frequency: +5% to -5%
Momentary voltage
dip capability (*6)
Operation will continue with 165V or more. If voltage drops below 165V, operation will continue for up to 15 ms.
If "Continuous operation" is selected, the output frequency will be lowered to withstand the load until normal voltage is resumed.
Required power
supply capacity
[kVA] (*7)
0.4 0.7 1.3 2.2 3.1 5
5 7.2 9.7 15 20 24
29 29 38 47 56 69 93 111
EQ5 VT (Variable Torque) – 230V Series
Type
NEMA 1
OPEN CHASSIS
Applied Motor
Nominal (HP)
0.25
0.5 1 2 3 5 7.5
10
15
20
25
30
30 40 50 60 75 100 125 150
Model
EQ5-2XXX-XX
0P2
-N1
0P5
-N1
001
-N1
002
-N1
003
-N1
005
-N1
007
-N1
010
-N1
015
-N1
020
-N1
025
-N1
030
-N1
032
-N1
040
-C
050
-C
060
-C
075
-C
100
-C
125
-C
150
-C
Rated output
capacity [kVA] (*1)
0.6 1.2 2.0 3.2 4.4 6.8 8.8 12 17 22 27 31 35 46 58 72 86 113 138 165
Rated output
current [A] (*2)
1.5 3.0 5.0 8.0 11 17 22 29 42 55 6
8 80 87 115 145 180 215 283 346 415
Overload
capability
110% of rated output current for 1 min.
Starting torque
50% or more
Output
ratings
Rated output
voltage [V] (*3)
3-phase, 200V/50Hz, 200V,220V,230V/60Hz
Rated output
frequency [Hz]
50,60Hz
Input ratings
Phases, voltage,
frequency
3-phase, 200 to 230V, 50/60Hz
3-phase, 200 to 220V, 220 to 230V/50Hz
3-phase, 200 to 230V/60Hz
Voltage/frequency
variations
Voltage: +10% to -15% (Imbalance rate between phases: 2% or less (*5) , Frequency: +5% to -5%
Momentary voltage
dip capability (*6)
Operation will continue with 165V or more. If voltage drops below 165V, operation will continue for up to 15 ms.
If "Continuous operation" is selected, the output frequency will be lowered to withstand the load until normal voltage is resumed.
Required power
supply capacity
[kVA] (*7)
0.4 0.7 1.3 2.2 3.1 5 7.2 9.7 15 20 24
29 29 38 47 56 69 93 111 139