8-4 RS-485 Modbus RTU Serial Communications

The serial communications interface supports operation, configuration and monitoring of inverter
functions through an EIA/RS-485 connection. The serial interface is based on Modbus RTU
protocol. This protocol allows the inverter to function as an RTU slave on an industrial network.

8- 4-1 Transmission Specifications

Item

Specification

Physical level

EIA/RS-485

Transmission distance

1600 ft (500 m)

Number of nodes

32 total

Transmission speed

19200, 9600, 4800, 2400 [bits/s]

Transmission mode

Half duplex

Transmission protocol

Modbus RTU

Character code

Binary

Character length

8 bits

Error check

CRC

8- 4-2 Connection

Connection method:
Use shielded wire and connect to the control terminals (DX-, DX+ and SD). A terminating
resistor should be added between the data lines on the each end of the network. The value of
the terminating resistor depends on the characteristic impedance of the cable. A common
value is 120 ohms.

Control terminals:

Terminal

Designation

Terminal Name

Function Description

DX+

RS-485 communication data (+)

Input/output terminals for RS-485
communication.

DX-

RS-485 communication data (–)

SD

Cable shield

Electrically floating

8- 4-3 Serial Interface Configuration

Inverter function codes H30 to H39 are used to configure the serial interface parameters, such
as device address, baud rate and error response.

8- 4- 4 Modbus RTU Functions

The following RTU functions are supported. The maximum number of consecutive parameters
for function 03 and 16 messages is 16.

Code

Description

03

Read Holding Registers (16 registers maximum)

06

Preset Single Register

16

Preset Multiple Registers (16 registers maximum)