HP Anab EQ5 User Manual
Page 24
EQ5 AC Drive Operations Manual
______________________________________________________________________
TECO – Westinghouse Motor Company Control Terminal Designations & Wiring 18
Digital input
FWD
Forward operation /
stop command
Forward operation (when FWD-CM is on) or deceleration
and stop (when FWD-CM is open).
REV
Reverse operation /
stop command
Reverse operation (when REV-CM is on) or deceleration
and stop (when REV-CM is open).
X1
Digital input 1
The coast-to-stop command, external alarm, alarm reset,
multi-step frequency selection, and other functions (from an
external circuit) can be assigned to terminals X1 to X9. For
details, see "Setting the Terminal Functions E01 to E09" in
Section 5.3 Function Explanation.
*
Item min.
typ.
max.
Operating voltage
ON
2V
-
2V
OFF 22V 24V 27V
Operating current
level
ON -
3.2mA
4.5mA
Leakage current
OFF
-
-
0.5mA
FWD, REV
X1 – X9
CM
PLC
6.8k
Ω
+24V
0V
X2
Digital input 2
X3
Digital input 3
X4
Digital input 4
X5
Digital input 5
X6
Digital input 6
X7
Digital input 7
X8
Digital input 8
X9
Digital input 9
CM
Common terminal
Common terminal for digital inputs ,FMP and P24.
P24
Control Unit power
Supply
+24VDC power supply for control input. Maximum output
current 100mA
PLC
PLC signal power
Used to connect to a PLC power supply output 22 to 27
VDC, input signals set to sink logic operation.
Analog output
FMA
(11 Com)
Analog monitor
Analog output DC voltage 0 to +10V DC.
The signal is selected to indicate one of the following:
-Output frequency (before slip compensation)
-Power consumption
-Output frequency (after slip compensation)
-PID feedback value
-Output current
-PG feedback value
-Output voltage
-DC link circuit voltage
-Output torque
-Load factor
*Minimum load resistance: 5k
Ω