beautypg.com

HP Anab EQ5 User Manual

Page 24

background image


EQ5 AC Drive Operations Manual

______________________________________________________________________

TECO – Westinghouse Motor Company Control Terminal Designations & Wiring 18

Digital input

FWD

Forward operation /
stop command

Forward operation (when FWD-CM is on) or deceleration
and stop (when FWD-CM is open).

REV

Reverse operation /
stop command

Reverse operation (when REV-CM is on) or deceleration
and stop (when REV-CM is open).

X1

Digital input 1

The coast-to-stop command, external alarm, alarm reset,
multi-step frequency selection, and other functions (from an
external circuit) can be assigned to terminals X1 to X9. For
details, see "Setting the Terminal Functions E01 to E09" in
Section 5.3 Function Explanation. input circuit>
*

Item min.

typ.

max.

Operating voltage

ON

2V

-

2V

OFF 22V 24V 27V

Operating current
level

ON -

3.2mA

4.5mA

Leakage current

OFF

-

-

0.5mA

FWD, REV

X1 – X9

CM

PLC

6.8k

+24V

0V

X2

Digital input 2

X3

Digital input 3

X4

Digital input 4

X5

Digital input 5

X6

Digital input 6

X7

Digital input 7

X8

Digital input 8

X9

Digital input 9

CM

Common terminal

Common terminal for digital inputs ,FMP and P24.

P24

Control Unit power
Supply

+24VDC power supply for control input. Maximum output
current 100mA

PLC

PLC signal power

Used to connect to a PLC power supply output 22 to 27
VDC, input signals set to sink logic operation.

Analog output

FMA
(11 Com)

Analog monitor

Analog output DC voltage 0 to +10V DC.
The signal is selected to indicate one of the following:
-Output frequency (before slip compensation)
-Power consumption
-Output frequency (after slip compensation)
-PID feedback value
-Output current
-PG feedback value
-Output voltage
-DC link circuit voltage
-Output torque
-Load factor
*Minimum load resistance: 5k







This manual is related to the following products: