EQ5 AC Drive Operations Manual

______________________________________________________________________

TECO – Westinghouse Motor Company Control Terminal Designations & Wiring 19

Pulse output

FMP
(CM Com)

Frequency monitor
(pulse output)

Outputs a pulse frequency indicating the same as that of the
analog FMA signal.

Transistor

output

Y1 Transistor

output1

A running signal, frequency equivalence signal, overload
early warning signal, and other signals from the inverter are
output (as a transistor output) to terminals Y1-Y4. For
details, see "Setting the Terminal Functions E20 to E23" in
Section 5.3 Function Explanation

Transistor output circuit specifications

Item min.

typ.

max.

Operating
voltage

ON

-

2V

3V

OFF

-

24V

27V

Maximum load current

ON

-

-

50mA

Leakage current

OFF

-

-

0.1mA

Y2 Transistor

output2

Y3 Transistor

output3

Y4 Transistor

output4

CME

Transistor output
common

Common terminal for transistor output signals
This terminal is insolated from terminals [CM] and [11].

Relay outputs

30A,30B,
30C

Alarm output for
any fault

If the inverter is stopped by an alarm (protective function),
the relay (SPDT) will activate.
Contact rating: 250 VAC, .03A - 48V DC, 0.5A
The activation mode can be selected for normal or alarm
operation.

Y5A,Y5C

Multipurpose-signal
relay output

The activation signals can be the same as the Y1 -Y4
outputs above.
The contact ratings are the same as that of the alarm output
above.

Communication

DX+, DX-

RS485
Modbus RTU
communication

Terminals for RS485 communication (Modbus RTU). UP to
31 inverters can be connected using the daisy chain method.

SD

Communication-
cable shield
connection terminal

Terminal for connecting the shield of the communication
cable. The terminal is electrically floating.


(1) Analog input terminals (13,12,V2,C1,and 11)

a. These terminals receive analog signals that may be affected by external noise. The cables should be as short

as possible (66ft /20m or less), be shielded twisted cable, and must be properly grounded. If the cables are
affected by externally induced noise, the shielding effect may be improved by connecting the shield to terminal
[11]. (see Fig. 2-3-8)


b. If contacts are used to connect to these circuits, twin (bifurcated type) contacts for handling low level

signals must be used. A contact must not be connected to terminal [11].

c. If an external analog signal output device is connected to these terminals, it may malfunction as a

result of inverter noise. To prevent malfunction, connect a ferrite core or capacitor to the external analog
signal output device as shown in Fig. 2-3-9.