beautypg.com

HP Anab EQ5 User Manual

Page 83

background image

TECO

–Westinghouse Motor Company Function Explanation 77





PID control detects the amount of control (feedback

amount) from a sensor of the control target, then
compares it with the target value (e.g., reference
temperature). If the values differ, this function performs a
control to eliminate the deviation. In other words, this
control matches the feedback amount with the target
value.

This function can be used for flow control, pressure control,
temperature control, and other process controls.

Target

value

P

Drive

section

Control

target

I

D

+

+

+

+

-

Feedback amount

Forward or reverse operations can be selected for PID

controller output. This enables motor revolutions to be
faster or lower according to PID controller output

This function cannot be used when the motor 2 is

selected.

H 2 0

P I D M O D E

Set value 0: No operation

1: Forward operation
2: Reverse operation

For

wa

rd

op

erati

on

Rev

er

se

op

erati

on

Maximum
frequency

0

0%

100%

PID output

Inverter output

frequency

The target value can be entered using F01, "Frequency

setting 1," or directly from the keypad panel. Select any
terminal of Terminals X1 (E01) to X9 (E09) and set value
11 (frequency setting switching).

For entry from F01, "Frequency setting 1," input an OFF
signal to the selected terminal. For direct entry from the
keypad panel, turn on the selected terminal.
For the target value and feedback amount, the process

amount can be displayed according to the values set in
E40, "Display coefficient A," and E41, "Display
coefficient B."





This function selects the feedback amount input terminal
and electrical specifications of the terminal. Select a value
from the table below according to sensor specifications.

Set value

Descriptions

0

Control terminal 12, forward operation (0 to
10V voltage input)

1

Control terminal C1, forward operation (4 to
20mA current input)

2

Control terminal 12, reverse operation (10
to 0V voltage input)

3

Control terminal C1, reverse operation (20
to 4mA current input)

For

wa

rd

op

er

at

ion

Rev

er

se

op

erati

on

100%

0%

0V

4mA

10V

20mA

Input

Feedback amount

Only positive values can be input for this feedback amount
of PID control. Negative values (e.g., 0 to -10V, -10 to 0V)
cannot be input, thereby the function cannot be used for a
reverse operation by an analog signal.

H 2 1

F B

S I G N A L

Target value or
feedback amount

Display

Display coefficient A

Display coefficient B

0%

100%

H21

PID control (Feedback signal)

H25

PID control (Feedback filter)

H20

PID control (Mode select)

This manual is related to the following products: