EQ5 AC Drive Operations Manual

________________________________________________________________________

TECO – Westinghouse Motor Company Installation Environment & Method 5

2. Installation and Electrical Connections

2-1 Operating Environment

Install this product in a location that meets the conditions listed in Table 2-1-1

Table 2-1-1 Operating Environment

Table 2-1-2 Output Current Reduction

Rate Based on Altitude

Item Specifications

Location Indoors

Altitude

Output current

reduction rate

Ambient

temperature

-10Cº to +50ºC (14ºF to 122ºF) -
For products of 30HP/CT,
40HP/VT or less, the ventilating
covers must be removed if the
ambient temperature exceeds
+40ºC (104ºF)


3300ft or lower (1000m)

1.00

3300-4950ft

(1000 to 1500m)

0.97

4950-6600ft

(1500 to 2000m)

0.95

Relative

humidity

5 to 95% non-condensing

6600-8250ft

(2000 to 2500m)

0.91

8250-9900ft

(2500 to 3000m)

0.88

Atmosphere

The product must not be exposed
to dust, direct sunlight, corrosive
gas, oil mist, vapor, or water.
There must be a minimum salt
content in the atmosphere. Do not
store where condensation may
occur as a result of sudden
changes in temperature.

Fig. 2-2-1

30HP/CT, 40HP/VT or less:
Gap X can be 0.
(side-by- side installation)

40HP/CT, 50HP/VT or more:

Gap X >= 2.0” (50mm)

Altitude

1000 m (3300 feet) or lower - For
altitudes above 1000 m (3300
feet), see Table 2-1-2.

Vibration

3mm peak from 2 to 9Hz, 9.8m/s

2

from 9 to 20Hz,
2m/s

2

from 20-55Hz, 1m/s

2

from

55 to 200Hz.

2-2 Installation Method

1. Mounting, dimensional and weight information for all of the inverter models, is covered in Sec. 8-3 of

this manual. Select the model being used and prepare the installation.
2. Securely fasten the product in a vertical upright position on a solid structure with the product

logo facing the front. Do not mount the product upside down or install in a horizontal position
as proper ventilation will be inhibited.
3. As heat is generated during inverter operation, the spaces shown in Fig. 2-2-1 are required to
ensure sufficient cooling. Since heat radiates upward, do not install the product beneath
heat sensitive equipment.
4. During operation, the heat sink may reach a temperature of 90ºC (194ºF), therefore ensure that
the material surrounding the product can withstand this temperature.

DANGER

Install this product on nonflammable material such as metal.