–Westinghouse Motor Company Function Explanation 46

5-2 Function Explanation



Setting can be made so that a set value cannot be
changed by keypad panel operation.




Setting range

0 : The data can be changed.

1 : The data cannot be changed.

Setting procedure

0 to 1: Press the and keys simultaneously

to change the value from 0 to 1, then press the

to validate the change.

1 to 0: Press the and keys simultaneously

to change the value from 1 to 0, then press the

key to validate the change.


This function selects the frequency
setting method.



0 : Setting by keypad panel operation ( key)
1 : Setting by voltage input (terminal

12

(0 to +10V)

+ terminal [V2](0 to +10V) )
2: Setting by current input (terminal

C1

(4 to 20mA)).

3: Setting by voltage input + current input (terminal

12

+ terminal

C1

) (-10 to +10V + 4 to 20mA).

4: Reversible operation with polarity ( terminal

12

(-10 to +10V))
5: Reversible operation with polarity ( terminal

12

+[V2]+[V1](Option) (-10 to +10V))
6: Inverse mode operation
(terminal

12

+[V2] (+10V to 0 ))

7: Inverse mode operation
(terminal

C1

(20 to 4mA))

8: Setting by UP/DOWN control mode 1

(initial value = 0) (Terminals

UP

and

DOWN

)

9: Setting by UP/DOWN control mode 2
(initial value =last final value)
(terminals

UP

and

DOWN

)

See the function explanation of E01 to E09 for details.
10: Setting by pattern operation
See the function explanation C21 to C28 for details.

11: Setting by digital input or pulse train

* Optional. For details, see the instruction manual on options.


Set value:1,3

Set value:4,5

-10 0 +10 [V]

- Maximum frequency

Maximum frequency

Frequency setting value

Analog input terminal
[12] , [V2]

Inverse operation
(set value::6)

Forward operation
(set value: 1, 3, 4, 5)

0 4 20 [mA]

Maximum frequency

0

Frequency setting value

Analog input terminal
[C1]

Inverse operation
(set value: 7)

Forward operation
(set value: 2)

This function sets the operation command input

method.

Setting range 0: Key pad operation

( keys).

Press the for forward operation.

Press the for reverse operation.

Press the for deceleration to a stop.
Input from terminals

FWD

and

REV

is ignored.

(LOCAL)
1: Terminal operation( key active)


2: Terminal operation( key inactive)


3: Terminal operation( key active) through

software.

4: Terminal operation( key inactive) through
software.
* - This function can only be changed when terminals FWD
and REV are open.
- REMOTE/LOCAL switching from the keypad panel
automatically changes the set value of this function.
- REMOTE/LOCAL can be changed by pressing the
key and key simultaneously.

FWD

FWD

F:

Fundamental function

F00

Data protection

FWD

FWD

FWD

FWD

FWD

FWD

F01

Frequency command 1

F02

Operation method

Related

functions:

E01 to E09

(Set value

17,18)

Forward / Inverse operation

Related

functions:

C21to C28

Related functions:

E01 to E09

(Set value 21)

F 0 0

D A T A

P R T C

Related functions

E01 to E09

(Set values 19)

F 0 1

F R E Q

C M D 1

Related functions

E01 to E09

(Set values 17, 18)

C30

F 0 2

O P R

M E T H O D

Related functions:

E01 to E09

(Set value 21)

FUNC
DATA

FUNC
DATA

FWD

REV

STOP

STOP

STOP

FWD

REV

STOP

STOP

RESET

STOP

STOP

STOP

STOP