HP Anab EQ5 User Manual
Page 52
TECO
–Westinghouse Motor Company Function Explanation 46
5-2 Function Explanation
Setting can be made so that a set value cannot be
changed by keypad panel operation.
Setting range
0 : The data can be changed.
1 : The data cannot be changed.
Setting procedure
0 to 1: Press the and keys simultaneously
to change the value from 0 to 1, then press the
to validate the change.
1 to 0: Press the and keys simultaneously
to change the value from 1 to 0, then press the
key to validate the change.
This function selects the frequency
setting method.
0 : Setting by keypad panel operation ( key)
1 : Setting by voltage input (terminal
12
(0 to +10V)
+ terminal [V2](0 to +10V) )
2: Setting by current input (terminal
C1
(4 to 20mA)).
3: Setting by voltage input + current input (terminal
12
+ terminal
C1
) (-10 to +10V + 4 to 20mA).
4: Reversible operation with polarity ( terminal
12
(-10 to +10V))
5: Reversible operation with polarity ( terminal
12
+[V2]+[V1](Option) (-10 to +10V))
6: Inverse mode operation
(terminal
12
+[V2] (+10V to 0 ))
7: Inverse mode operation
(terminal
C1
(20 to 4mA))
8: Setting by UP/DOWN control mode 1
(initial value = 0) (Terminals
UP
and
DOWN
)
9: Setting by UP/DOWN control mode 2
(initial value =last final value)
(terminals
UP
and
DOWN
)
See the function explanation of E01 to E09 for details.
10: Setting by pattern operation
See the function explanation C21 to C28 for details.
11: Setting by digital input or pulse train
* Optional. For details, see the instruction manual on options.
Set value:1,3
Set value:4,5
-10 0 +10 [V]
- Maximum frequency
Maximum frequency
Frequency setting value
Analog input terminal
[12] , [V2]
Inverse operation
(set value::6)
Forward operation
(set value: 1, 3, 4, 5)
0 4 20 [mA]
Maximum frequency
0
Frequency setting value
Analog input terminal
[C1]
Inverse operation
(set value: 7)
Forward operation
(set value: 2)
This function sets the operation command input
method.
Setting range 0: Key pad operation
( keys).
Press the for forward operation.
Press the for reverse operation.
Press the for deceleration to a stop.
Input from terminals
FWD
and
REV
is ignored.
(LOCAL)
1: Terminal operation( key active)
2: Terminal operation( key inactive)
3: Terminal operation( key active) through
software.
4: Terminal operation( key inactive) through
software.
* - This function can only be changed when terminals FWD
and REV are open.
- REMOTE/LOCAL switching from the keypad panel
automatically changes the set value of this function.
- REMOTE/LOCAL can be changed by pressing the
key and key simultaneously.
FWD
FWD
F:
Fundamental function
F00
Data protection
FWD
FWD
FWD
FWD
FWD
FWD
F01
Frequency command 1
F02
Operation method
Related
functions:
E01 to E09
(Set value
17,18)
Forward / Inverse operation
Related
functions:
C21to C28
Related functions:
E01 to E09
(Set value 21)
F 0 0
D A T A
P R T C
Related functions
E01 to E09
(Set values 19)
F 0 1
F R E Q
C M D 1
Related functions
E01 to E09
(Set values 17, 18)
C30
F 0 2
O P R
M E T H O D
Related functions:
E01 to E09
(Set value 21)
FUNC
DATA
FUNC
DATA
FWD
REV
STOP
STOP
STOP
FWD
REV
STOP
STOP
RESET
STOP
STOP
STOP
STOP