HP Anab EQ5 User Manual

Page 56

background image

TECO

–Westinghouse Motor Company Function Explanation 50

Output frequency f

0

(Hz)

O

pe

rati

on

l

ev

el

c

urren

t (%

)

53

Fe x 0.33

Fe x 0.83

fe

100

110kW or above

(%)

Operation level current and output frequency

fe= fb (fb

60Hz)

60Hz (fb

60Hz)

fb:

Base frequency

(When F10 = 1

)

85

90

Output frequency f

0

(Hz)

O

pe

rati

on

l

ev

el

c

urren

t (%

)

53

Fe x 0.33

Fe x 0.83

fe

100

110kW or above

(%)

Operation level current and output frequency

fe= fb (fb

60Hz)

60Hz (fb

60Hz)

fb:

Base frequency

(When F10 = 1

)

85

90

The time from when 150% of the operation level

current flows continuously to when he electronic
thermal O/L relay activates can be set.
The setting range is 0.5 to 75.0 minutes (in 0.1
minute steps).


0

5

10

15

20

0

50

100

150

200

O

p

e

ra

tio

n

t

im

e

(m

in

F12=0.5

F12=10

F12=5

changed by F12

(output current/operation level current)
x 100(%)

Current-Operation time Characteristics









This function controls the frequent use and continuous
operating time of the braking resistor to prevent the
resistor from overheating.


Inverter capacity

Operation

EQ5:10HP/CT,
15HP/VT or less

0: Inactive
2: Active

(DB***-2C/4C external braking resistor)

EQ5:

15HP/CT,

20HP/VT or more

0: Inactive

When the setting value is selected to "2", the type of

braking resistor and connection circuit are set by U59.
The details are referred to the function : U59.

F 1 2

T I M E

C N S T 1

Electric thermal O/L relay (for breaking resistor)

F13

F 1 3

D B R

O L

Related functions:

U59

75HP to 125HP

150HP or above

This manual is related to the following products: