Select one of the following two types of overload early

warning: early warning by electronic thermal O/L relay
function or early warning by output current.

Set value 0: Electronic thermal O/L relay

1: Output current

Set
value

Function

Description

0

Electronic
thermal
O/L relay

Overload early warning by electronic
thermal O/L relay (having inverse-time
characteristics) to output current.
The operation selection and thermal
time constant for the inverse-time
characteristics are the same as those
of the electronic thermal O/L relay for
motor protection (F10 and F12).

1

Output
current

An overload early warning is issued
when output current exceeds the set
current value for the set time.
The figure of OL2(E37) is referred.

This function cannot be used when Motor 2 is selected.


This function determines the operation level of the

electronic thermal O/L relay or output current.

Setting range EQ5:Inverter rated output current x (5 to 150%)

The operation release level is 90% of the set value.

This function cannot be used when Motor 2 is selected.

This function is used when 1 (output current) is set to

"E33 Overload early warning (operation selection)."

Setting range: 0.1 to 60.0 seconds

Set the time from when the operation level is attained

until the overload early warning function is activated.



This function determines the operation (detection) level

of output frequency for “2nd Freq. level detection [FDT2]”.
The hysteresis width for operation release is set by the
function E32: FDT1 function signal (Hysteresis).

Setting range(Operation level) : EQ5: 0 to 120 Hz


This function determines the operation level of the output

current for “2nd OL level detection [OL2]”.

Setting range EQ5: Inverter rated output current x (5 to 150%)

The operation release level is 90% of the set value.

ON

E37 OL2 LEVEL

E35
OL TIMER

[OL2]

Output current

OL2 LEVEL x 90%

(E34 OL1 LEVEL)

(OL1 LEVEL x 90%)




These coefficients are conversion coefficients which are

used to determine the load and line speed and the target
value and feedback amount (process amount) of the PID
controller displayed on the LED monitor.

Setting range
Display coefficient A:-999.00 to 0.00 to +999.00
Display coefficient B:-999.00 to 0.00 to +999.00

Load and line speed

Use the display coefficient A.

Displayed value = output frequency x (0.01 to 200.00)

Although the setting range is ± 999.00, the effective
value range of display data is 0.01 to 200.00. Therefore,
values smaller or larger than this range are limited to a
minimum value of 0.01 or a maximum value of 200.00.

Target value and feedback amount of PID controller

Set the maximum value of display data in E40, "Display
coefficient A," and the minimum value in E41, "Display
coefficient B."

Displayed value = (target value or feedback amount)

x (display coefficient A - B)+B




E 3 3

O L

W A R N I N G

E 3 4

O L 1

L E V E L

E 3 5

O L 1

T I M E R

E 4 0

C O E F

A

E 4 1

C O E F

B

E34

OL function signal (Level)

E35

OL function signal (Timer)

Displayed value

A

Target value or
feedback amount

B

0%

100%

E40

Display coefficient A

E41

Display coefficient B

E33

OL function signal (mode select)

selection

E36

FDT2 function (Level)

E 3 6

F D T 2 L E V E L

E37

OL2 function (Level)

E 3 7

O L 2

L E V E L

E40

Display coefficient A

E41

Display coefficient B