EQ5 AC Drive Operations Manual
_______________________________________________________________________
TECO – Westinghouse Motor Company Parameters C20 – C33, P01 – P09 & H03 – H39 44
Para.
No.
NAME
LCD Display
Setting range
Unit
Min.
Unit
Factory setting
Change
During
Oper.
User
Set value
Remark
30HP/CT
40HP/VT
40HP/CT
50HP/VT
C20 JOG frequency
C20
JOG Hz
0.00 to 120.00Hz
Hz
0.01
5.00
N
C21 PATTERN (Mode select)
C21
PATTERN
0,1,2
-
-
0
N
C22 (Stage
1)
C22
STAGE 1
Operation time:0.00 to 6000s
F1 to F4 and R1 to R4
s
0.01
0.00 F1
Y
C23 (Stage
2)
C23
STAGE 2
0.00 F1
C24 (Stage
3)
C24
STAGE 3
0.00 F1
C25 (Stage
4)
C25
STAGE 4
0.00 F1
C26 (Stage
5)
C26
STAGE 5
0.00 F1
C27 (Stage
6)
C27
STAGE 6
0.00 F1
C28 (Stage
7)
C28
STAGE 7
0.00 F1
C30 Frequency command 2
C30
FREQ CMD 2
0 to 11 -
-
2
N
C31 Offset adjust (terminal [12])
C31
BIAS 12
-100.0 to +100.0%
%
0.1
0.0
Y
C32
C32
GAIN 12
0.0 to +200.0%
%
0.1
100.0
Y
C33 Analog setting signal filter
C33
REF FILTER
0.00 to 5.00s
s
0.01
0.05
Y
P Parameters
P01 Number of motor 1 poles
P01
M1 POLES
2 to 14
-
2
4
N
P02
Motor 1 (Capacity)
P02
M1-CAP
Up to 30[HP]: 0.01 to 60HP
HP 0.01
Motor Capacity
N
40[HP] and above: 0.01 to 800HP
P03
(Rated current)
P03
M1-Ir
0.00 to 2000A
A
0.01
Motor rated current
N
P04
(Tuning)
P04
M1 TUN1
0, 1, 2
-
-
0
N
P05 (On-line
Tuning)
P05
M1 TUN2
0, 1
-
-
0
N
P06
(No-load current)
P06
M1-Io
0.00 to 2000A
A
0.01
Standard Rated Value
N
P07
(%R1 setting)
P07
M1-%R1
0.00 to 50.00%
%
0.01
Standard Rated Value
Y
P08
(%X setting)
P08
M1-%X
0.00 to 50.00%
%
0.01
Standard Rated Value
Y
P09 Slip compensation control 1
P09
SLIP COMP1
0.00 to 15.00Hz
Hz
0.01
0.00
Y
H Parameters
H03 Data initializing
H03
DATA INIT
0, 1
-
-
0
N
H04 Auto-reset
(Times)
H04
AUTO-RESET
0, 1 to 10 times
-
1
0
Y
H05
(Reset interval)
H05
RESET INT
2 to 20s
s
1
5
Y
H06 Fan stop operation
H06
FAN STOP
0, 1
-
-
0
Y
H07 ACC/DEC pattern
(Mode select)
H07
ACC PTN
0,1,2,3
-
-
0
N
H08 Rev. phase sequence lock
H08
REV LOCK
0, 1
-
-
0
N
H09 Start mode
H09
START MODE
0, 1, 2
-
-
0
N
H10 Energy-saving operation
H10
ENERGY SAV
0, 1
-
-
1
Y
H11 DEC mode
H11
DEC MODE
0, 1
-
-
0
Y
H12 Instantaneous OC limiting
H12
INST CL
0, 1
-
-
1
N
H13 Auto-restart
(Restart time)
H13
RESTART t
0.1 to 10.0s
s
0.1
0.1
N
H14
(Freq. fall rate)
H14
FALL RATE
0.00 to 100.00Hz/s
Hz/s
0.01
10.00
Y
H15 (Holding DC voltage)
H15
HOLD V
3ph 230V class: 200 to 300V
V
1
230V class:235V
Y
3ph 460V class: 400 to 600V
460V class:470V
H16
(OPR command selfhold time)
H16
SELFHOLD t
0.0 to 30.0s, 999
s
0.1
999
N
H19 Active drive
H19
AUT RED
0, 1
-
-
0
Y
H20
PID control
(Mode select)
H20
PID MODE
0, 1, 2
-
-
0
N
H21
(Feedback signal)
H21
FB SIGNAL
0, 1, 2, 3
-
-
1
N
H22
(P-gain)
H22
P-GAIN
0.01 to 10.00 times
-
0.01
0.1
Y
H23
(I-gain)
H23
I-GAIN
0.0 , 0.1 to 3600s
s
0.1
0.0
Y
H24
(D-gain)
H24
D-GAIN
0.00s , 0.01 to 10.0s
s
0.01
0.00
Y
H25
(Feedback filter)
H25
FB FILTER
0.0 to 60.0s
s
0.1
0.5
Y
H26
PTC thermistor
(Mode select)
H26
PTC MODE
0, 1
V 0.01
0 Y
H27
(Level)
H27
PTC LEVEL
0.00 to 5.00V
1.60
Y
H30 Serial link
(Function select)
H30
LINK FUNC
0, 1, 2, 3
-
-
0
Y
H31
(Address)
H31
ADDRESS
0 (broadcast), 1 to 247
-
1
1
N
H32
(Mode select on no response error)
H32
MODE ON ER
0, 1, 2, 3
-
-
0
Y
H33 (Timer)
H33
TIMER
0.0 to 60.0s
s
0.1
2.0
Y
H34 Modbus-RTU (Baud
rate)
H34
BAUD RATE
0, 1, 2, 3
-
-
1
Y
H35 (Data
length)
H35
LENGTH
0 (8-bit fixed)
-
-
0
Y
H36 (Parity
check)
H36
PARITY
0, 1, 2
-
-
0
Y
H37 (Stop
bits)
H37
STOP BITS
0(2bit), 1(1bit)
-
-
0
Y
H38
(No response error detection time)
H38
NO RES t
0 (No detection), 1 to 60s
s
1
0
Y
H39 (Response
interval)
H39
INTERVAL
0.00 to 1.00s
s
0.01
0.01
Y