EQ5 AC Drive Operations Manual

_______________________________________________________________________

TECO – Westinghouse Motor Company Parameters C20 – C33, P01 – P09 & H03 – H39 44

Para.

No.

NAME

LCD Display

Setting range

Unit

Min.

Unit

Factory setting

Change

During

Oper.

User

Set value

Remark

30HP/CT
40HP/VT

40HP/CT
50HP/VT

C20 JOG frequency

C20

JOG Hz

0.00 to 120.00Hz

Hz

0.01

5.00

N

C21 PATTERN (Mode select)

C21

PATTERN

0,1,2

-

-

0

N

C22 (Stage

1)

C22

STAGE 1

Operation time:0.00 to 6000s

F1 to F4 and R1 to R4

s

0.01

0.00 F1

Y

C23 (Stage

2)

C23

STAGE 2

0.00 F1

C24 (Stage

3)

C24

STAGE 3

0.00 F1

C25 (Stage

4)

C25

STAGE 4

0.00 F1

C26 (Stage

5)

C26

STAGE 5

0.00 F1

C27 (Stage

6)

C27

STAGE 6

0.00 F1

C28 (Stage

7)

C28

STAGE 7

0.00 F1

C30 Frequency command 2

C30

FREQ CMD 2

0 to 11 -

-

2

N

C31 Offset adjust (terminal [12])

C31

BIAS 12

-100.0 to +100.0%

%

0.1

0.0

Y

C32

C32

GAIN 12

0.0 to +200.0%

%

0.1

100.0

Y

C33 Analog setting signal filter

C33

REF FILTER

0.00 to 5.00s

s

0.01

0.05

Y

P Parameters

P01 Number of motor 1 poles

P01

M1 POLES

2 to 14

-

2

4

N

P02

Motor 1 (Capacity)

P02

M1-CAP

Up to 30[HP]: 0.01 to 60HP

HP 0.01

Motor Capacity

N

40[HP] and above: 0.01 to 800HP

P03

(Rated current)

P03

M1-Ir

0.00 to 2000A

A

0.01

Motor rated current

N

P04

(Tuning)

P04

M1 TUN1

0, 1, 2

-

-

0

N

P05 (On-line

Tuning)

P05

M1 TUN2

0, 1

-

-

0

N

P06

(No-load current)

P06

M1-Io

0.00 to 2000A

A

0.01

Standard Rated Value

N

P07

(%R1 setting)

P07

M1-%R1

0.00 to 50.00%

%

0.01

Standard Rated Value

Y

P08

(%X setting)

P08

M1-%X

0.00 to 50.00%

%

0.01

Standard Rated Value

Y

P09 Slip compensation control 1

P09

SLIP COMP1

0.00 to 15.00Hz

Hz

0.01

0.00

Y

H Parameters

H03 Data initializing

H03

DATA INIT

0, 1

-

-

0

N

H04 Auto-reset

(Times)

H04

AUTO-RESET

0, 1 to 10 times

-

1

0

Y

H05

(Reset interval)

H05

RESET INT

2 to 20s

s

1

5

Y

H06 Fan stop operation

H06

FAN STOP

0, 1

-

-

0

Y

H07 ACC/DEC pattern

(Mode select)

H07

ACC PTN

0,1,2,3

-

-

0

N

H08 Rev. phase sequence lock

H08

REV LOCK

0, 1

-

-

0

N

H09 Start mode

H09

START MODE

0, 1, 2

-

-

0

N

H10 Energy-saving operation

H10

ENERGY SAV

0, 1

-

-

1

Y

H11 DEC mode

H11

DEC MODE

0, 1

-

-

0

Y

H12 Instantaneous OC limiting

H12

INST CL

0, 1

-

-

1

N

H13 Auto-restart

(Restart time)

H13

RESTART t

0.1 to 10.0s

s

0.1

0.1

N

H14

(Freq. fall rate)

H14

FALL RATE

0.00 to 100.00Hz/s

Hz/s

0.01

10.00

Y

H15 (Holding DC voltage)

H15

HOLD V

3ph 230V class: 200 to 300V

V

1

230V class:235V

Y

3ph 460V class: 400 to 600V

460V class:470V

H16

(OPR command selfhold time)

H16

SELFHOLD t

0.0 to 30.0s, 999

s

0.1

999

N

H19 Active drive

H19

AUT RED

0, 1

-

-

0

Y

H20

PID control

(Mode select)

H20

PID MODE

0, 1, 2

-

-

0

N

H21

(Feedback signal)

H21

FB SIGNAL

0, 1, 2, 3

-

-

1

N

H22

(P-gain)

H22

P-GAIN

0.01 to 10.00 times

-

0.01

0.1

Y

H23

(I-gain)

H23

I-GAIN

0.0 , 0.1 to 3600s

s

0.1

0.0

Y

H24

(D-gain)

H24

D-GAIN

0.00s , 0.01 to 10.0s

s

0.01

0.00

Y

H25

(Feedback filter)

H25

FB FILTER

0.0 to 60.0s

s

0.1

0.5

Y

H26

PTC thermistor

(Mode select)

H26

PTC MODE

0, 1

V 0.01

0 Y

H27

(Level)

H27

PTC LEVEL

0.00 to 5.00V

1.60

Y

H30 Serial link

(Function select)

H30

LINK FUNC

0, 1, 2, 3

-

-

0

Y

H31

(Address)

H31

ADDRESS

0 (broadcast), 1 to 247

-

1

1

N

H32

(Mode select on no response error)

H32

MODE ON ER

0, 1, 2, 3

-

-

0

Y

H33 (Timer)

H33

TIMER

0.0 to 60.0s

s

0.1

2.0

Y

H34 Modbus-RTU (Baud

rate)

H34

BAUD RATE

0, 1, 2, 3

-

-

1

Y

H35 (Data

length)

H35

LENGTH

0 (8-bit fixed)

-

-

0

Y

H36 (Parity

check)

H36

PARITY

0, 1, 2

-

-

0

Y

H37 (Stop

bits)

H37

STOP BITS

0(2bit), 1(1bit)

-

-

0

Y

H38

(No response error detection time)

H38

NO RES t

0 (No detection), 1 to 60s

s

1

0

Y

H39 (Response

interval)

H39

INTERVAL

0.00 to 1.00s

s

0.01

0.01

Y