TECO – Westinghouse Motor Company Standard Specifications Notes con’t 106

(*4) The taps within the inverter must be changed for an input power supply rated at 380 to 398V/50 Hz or 380 to 430V/60 Hz.

(*5) If the imbalance between phases exceeds 2%, use a power-factor correcting DC reactor (DCR).

( Max. Voltage [V] - Min. Voltage [V] )

Imbalance rate between phases [%] = x 67[%]

3-phase average voltage [V]

(*6) The test was conducted under the standard load conditions stipulated by the JEMA committee (at the load equivalent to 85% of the

nominal applied motor HP).

(*7) Indicates the values required when using a power-factor correcting DC reactor (DCR) with a loaded nominal applied motor. (optional for inverters of

75HP/CT, 100HP/VT or less)