beautypg.com

E: extension terminal functions – HP Anab EQ5 User Manual

Page 63

background image

TECO

–Westinghouse Motor Company Function Explanation 57

ON

ON

ON

ON

ON

ON

FWD

REV

HLD

O

utpu

t

frequ

ency

Forward
rotation

Reverse
rotation

Ignore

d.






Each function of digital input terminals X1 to X9 can be

set as codes.

Set value

Function

0,1,2,3

Multistep frequency selection (1 to 15 steps) [SS1],[SS2],[SS4],[SS8]

4,5

Acceleration and deceleration time selection (3 steps) [RT1],[RT2]

6

Self-hold selection [HLD]

7

Coast-to-stop command [BX]

8

Alarm reset [RST]

9

External alarm [THR]

10

Jogging [JOG]

11

Frequency setting 2/frequency setting 1 [Hz2/Hz1]

12

Motor 2/motor 1 [M2/M1]

13

DC injection brake command [DCBRK]

14

Torque limit 2/torque limit 1 [TL2/TL1]

15

Switching operation from line to inverter (50Hz) [SW50]

16

Switching operation from line to inverter (60Hz) [SW60]

17

UP command [UP]

18

DOWN command [DOWN]

19

Edit permission command (data change permission) [WE-KP]

20

PID control cancellation [Hz/PID]

21

Forward/inverse switching (terminals 12 and C1) [IVS]

22

Interlock (52-2) [IL]

24

Link operation selection (Standard:RS-485, Option: BUS) [LE]

25

Universal DI [U-DI]

26

Start characteristics selection [STM]

30

Forced stop command [STOP1]

31

Forced stop command with Deceleration time 4 [STOP2]

35

Frequency setting 1 / Frequency setting 2 [Hz1/Hz2]

Note: Data numbers which are not set in the functions

from E01 to E09, are assumed to be inactive.

The frequency can be switched to a preset frequency in
function codes C05 to C19 by switching the external digital
input signal. Assign values 0 to 3 to the target digital input
terminal. The combination of input signals determines the
selected frequency.

Combination of set
value input signals

Frequency selected

3

[SS8]

2

[SS4]

1

[SS2]

0

[SS1]

off

off

off

off

Assigned by F01 or C30

off

off

off

on

C05 MULTI Hz-1

Setting range

EQ5:0.00 to 120.00Hz

off

off

on

off

C06 MULTI Hz-2

off

off

on

on

C07 MULTI Hz-3

off

on

off

off

C08 MULTI Hz-4

off

on

off

on

C09 MULTI Hz-5

off

on

on

off

C10 MULTI Hz-6

off

on

on

on

C11 MULTI Hz-7

on

off

off

off

C12 MULTI Hz-8

on

off

off

on

C13 MULTI Hz-9

on

off

on

off

C14 MULTI Hz-10

on

off

on

on

C15 MULTI Hz-11

on

on

off

off

C16 MULTI Hz-12

on

on

off

on

C17 MULTI Hz-13

on

on

on

off

C18 MULTI Hz-14

on

on

on

on

C19 MULTI Hz-15



The acceleration and deceleration time can be switched to
a preset time in function codes E10 to E15 by switching the
external digital input signal. Assign values 4 and 5 to the
target digital input terminal. The combination of input
signals determines the acceleration and deceleration times.

Combination of
set value input
signals

Acceleration and deceleration times selected

5

[RT2]

4

[RT1]

off

off

F07 ACC TIME1
F08 DEC TIME1

Setting range

0.01 to 3600s

off

on

E10 ACC TIME2
E11 DEC TIME2

on

off

E12 ACC TIME3
E13 DEC TIME3

on

on

E14 ACC TIME4
E15 DEC TIME4

This selection is used for 3-wire operation. The FWD or
REV signal is self-held when [HLD] is on, and the self-hold
is cleared when [HLD] is turned off. To use this [HLD]
terminal function, assign 6 to the target digital input
terminal.

E 0 1

X 1

F U N C

E 0 2

X 2

F U N C

E 0 3

X 3

F U N C

E 0 4

X 4

F U N C

E 0 5

X 5

F U N C

E 0 6

X 6

F U N C

E 0 7

X 7

F U N C

E 0 8

X 8

F U N C

E 0 9

X 9

F U N C

E: Extension Terminal Functions

E01

X1 Terminal function

E09

X9 Terminal function

Multistep frequency selection [SS1][SS2][SS4][SS8]

Acceleration and deceleration time selection [RT1][RT2]

Related function

C05 to C19

Related function

F07F08

E10E15

3-wire operation stop command [HLD]