EQ5 AC Drive Operations Manual

______________________________________________________________________

TECO – Westinghouse Motor Company Trouble Shooting Chart 90

6-3.Trouble shooting

6-3-1 Protective function activation

(1) Overcurrent

YES

NO

NO

NO

YES

NO

NO

NO

YES

YES

YES

Are the motor connecting terminals (U, V, W) short-circuited or grounded?

Reduce the load or increase

the inverter capacity.

Is the load excessive?

Can the torque boost

amount be reduced?

Remove the short-circuit

and ground fault.

Prolong time settings.

Reduce the load or increase

the inverter capacity.

Is the torque boost

correct?

Reduce the torque boost.

Is the acceleration time

setting too short

compared with the load?

YES

Has the load changed

suddenly?

NO

NO

NO

YES

NO

Can the deceleration time
setting be prolonged?

YES

NO

Reduce the load or increase

the inverter capacity.

YES

Overcurrent

during acceleration

OC1

Is the deceleration time

setting too short compared

with the load?

Can the acceleration time

setting be prolonged?

YES

Overcurrent

during deceleration

OC2

Overcurrent

running at constant speed

OC3

NO

Faulty inverter or error

due to noise.

Consult with TWMC.

The braking method

requires inspection.

Contact TWMC.

(2) Ground fault

Note: The ground fault protective function is only available for inverters rated 40HP/CT,
50HP/VT and above.


(3) Fuse brown

Possible short-circuit

within the inverter.

Contact TWMC.

Fuse blown

FUS

Ground fault

EF

Remove the grounded part.

YES

Faulty inverter or error due to noise.

Contact TWMC.

NO

Is a part in the inverter output

circuit (cable, motor) grounded?

This manual is related to the following products: