EQ5 AC Drive Operations Manual

_______________________________________________________________________

TECO – Westinghouse Motor Company Parameter List F00 – F42 42

5. Parameters F,E,C,P,H, A and U

This section covers parameters F,E,C,P,H, A and U which can be set via the digital operator

(see Sect. 4) to achieve a specific performance for a particular application. For most general purpose
applications, the factory settings are sufficient and will not need to be changed. If the parameter
values are to be changed, it is recommended that resulting overall drive performance be evaluated to
avoid any unwanted performance issues.

5-1 Parameters Summary List
The following tables show the setting range, LCD readout, factory setting, and whether the value can
be changed while the drive is operational.

F Parameters

Para.

No.

NAME

LCD Display

Setting range

Unit

Min.

Unit

Factory setting

Change

During

Oper.

User

Set value

Remark


30HP/CT
40HP/VT

40HP/CT
50HP/VT

F00 Data protection

F00

DATA PRTC

0, 1

-

-

0

N

F01 Frequency command 1

F01

FREQ CMD 1

0 to 11

-

-

0

N

F02 Operation method

F02

OPR METHOD

0 to 4

-

-

0

N

F03 Maximum frequency 1

F03

MAX Hz-1

50 to 120Hz

Hz

1

60

N

F04 Base frequency 1

F04

BASE Hz-1

25 to 120Hz

Hz

1

60

N

F05 Rated voltage 1 (at Base frequency 1)

F05

RATED V-1

0V: (Output voltage proportional to

V

1

230:(230V class)

460:(460V class)

N

source voltage)

80 to 240V: (230V class)

320 to 480V: (460V class)

F06 Maximum voltage 1 (at Maximum frequency 1)

F06

MAX V-1

80 to 240V: (230V class)

V

1

230:(230V class)

N

320 to 480V: (460V class)

460:(460V class)

F07 Acceleration time 1

F07

ACC TIME1

0.01 to 3600s

s 0.01

6.0 20.0

Y

F08 Deceleration time 1

F08

DEC TIME1

F09 Torque boost 1

F09

TRQ BOOST1

0.0, 0.1 to 20.0

-

0.1

0.1

Y

F10 Electronic (Select)

F10

ELCTRN OL1

0, 1, 2

-

-

1

Y

F11 thermal 1( Level)

F11

OL LEVEL1

INV rated current 20 to 135%

A

0.01

Motor rated current

Y

F12 (Thermal time constant)

F12

TIME CNST1

0.5 to 75.0 min

min

0.1

5.0

10.0

N

F13

Electronic thermal overload relay

(for braking resistor)

F13

DBR OL

[Up to 10HP/CT, 15HP/VT]

- -

0

Y

0, 2

[15HP/CT, 20HP/VT and above ]

0

0

F14 Restart mode after momentary power failure

F14

RESTART

0 to 5

-

-

0

N

F15 Frequency limiter (High)

F15

H LIMITER

0-120Hz Hz

1

70

Y

F16 (Low)

F16

L LIMITER

N

F17 Gain (for freq. set signal)

F17

FREQ GAIN

0.0 to 200.0%

%

0.1

100.0

Y

F18 Bias frequency

F18

FREQ BIAS

-120.0 to +120.0Hz

Hz

0.1

0.0

Y

F20 DC brake (Starting freq.)

F20

DC BRK Hz

0.0 to 60.0Hz

Hz

0.1

0.0

Y

F21 (Braking level)

F21

DC BRK LVL

0 to 100%

%

1

0

F22 (Braking time)

F22

DC BRK t

0.0s (Inactive)

s

0.1

0.0

F23 Starting frequency (Freq.)

F23

START Hz

0.1 to 60.0Hz

Hz

0.1

0.5

N

F24 (Holding time)

F24

HOLDING t

0.0 to 10.0s

s

0.1

0.0

F25 Stop frequency

F25

STOP Hz

0.1 to 60.0Hz

Hz

0.1

0.2

N

F26 Motor sound (Carrier freq.)

F26

MTR SOUND

0.75 to 15kHz (Vary by HP)

kHz

1

2

Y

F27 (Sound tone)

F27

SOUND TONE

0 to 3

-

-

0

F30 FMA (Voltage adjust)

F30

FMA V-ADJ

0 to 200%

%

1

100

Y

F31 (Function)

F31

FMA FUNC

0 to 11

-

-

0

F33 FMP (Pulse rate)

F33

FMP PULSES

300 to 6000p/s (full scale)

p/s

1

1440

Y

F34 (Voltage adjust)

F34

FMP V-ADJ

0%, 1 to 200%

%

1

0

F35 (Function)

F35

FMP FUNC

0 to 10

-

-

0

F36 30RY operation mode

F36

30RY MODE

0, 1

-

-

0

Y

F40 Torque limiter 1 (Driving)

F40

DRV TRQ 1

20 to 150%, 999

%

1

999

Y

F41 (Braking)

F41

BRK TRQ 1

0%, 20 to 150%, 999

999

F42 Torque vector control 1

F42

TRQVECTOR1

0, 1

-

-

0

N