Eq5 ac drive operations manual, Parameters f,e,c,p,h, a and u – HP Anab EQ5 User Manual
Page 48
EQ5 AC Drive Operations Manual
_______________________________________________________________________
TECO – Westinghouse Motor Company Parameter List F00 – F42 42
5. Parameters F,E,C,P,H, A and U
This section covers parameters F,E,C,P,H, A and U which can be set via the digital operator
(see Sect. 4) to achieve a specific performance for a particular application. For most general purpose
applications, the factory settings are sufficient and will not need to be changed. If the parameter
values are to be changed, it is recommended that resulting overall drive performance be evaluated to
avoid any unwanted performance issues.
5-1 Parameters Summary List
The following tables show the setting range, LCD readout, factory setting, and whether the value can
be changed while the drive is operational.
F Parameters
Para.
No.
NAME
LCD Display
Setting range
Unit
Min.
Unit
Factory setting
Change
During
Oper.
User
Set value
Remark
30HP/CT
40HP/VT
40HP/CT
50HP/VT
F00 Data protection
F00
DATA PRTC
0, 1
-
-
0
N
F01 Frequency command 1
F01
FREQ CMD 1
0 to 11
-
-
0
N
F02 Operation method
F02
OPR METHOD
0 to 4
-
-
0
N
F03 Maximum frequency 1
F03
MAX Hz-1
50 to 120Hz
Hz
1
60
N
F04 Base frequency 1
F04
BASE Hz-1
25 to 120Hz
Hz
1
60
N
F05 Rated voltage 1 (at Base frequency 1)
F05
RATED V-1
0V: (Output voltage proportional to
V
1
230:(230V class)
460:(460V class)
N
source voltage)
80 to 240V: (230V class)
320 to 480V: (460V class)
F06 Maximum voltage 1 (at Maximum frequency 1)
F06
MAX V-1
80 to 240V: (230V class)
V
1
230:(230V class)
N
320 to 480V: (460V class)
460:(460V class)
F07 Acceleration time 1
F07
ACC TIME1
0.01 to 3600s
s 0.01
6.0 20.0
Y
F08 Deceleration time 1
F08
DEC TIME1
F09 Torque boost 1
F09
TRQ BOOST1
0.0, 0.1 to 20.0
-
0.1
0.1
Y
F10 Electronic (Select)
F10
ELCTRN OL1
0, 1, 2
-
-
1
Y
F11 thermal 1( Level)
F11
OL LEVEL1
INV rated current 20 to 135%
A
0.01
Motor rated current
Y
F12 (Thermal time constant)
F12
TIME CNST1
0.5 to 75.0 min
min
0.1
5.0
10.0
N
F13
Electronic thermal overload relay
(for braking resistor)
F13
DBR OL
[Up to 10HP/CT, 15HP/VT]
- -
0
Y
0, 2
[15HP/CT, 20HP/VT and above ]
0
0
F14 Restart mode after momentary power failure
F14
RESTART
0 to 5
-
-
0
N
F15 Frequency limiter (High)
F15
H LIMITER
0-120Hz Hz
1
70
Y
F16 (Low)
F16
L LIMITER
N
F17 Gain (for freq. set signal)
F17
FREQ GAIN
0.0 to 200.0%
%
0.1
100.0
Y
F18 Bias frequency
F18
FREQ BIAS
-120.0 to +120.0Hz
Hz
0.1
0.0
Y
F20 DC brake (Starting freq.)
F20
DC BRK Hz
0.0 to 60.0Hz
Hz
0.1
0.0
Y
F21 (Braking level)
F21
DC BRK LVL
0 to 100%
%
1
0
F22 (Braking time)
F22
DC BRK t
0.0s (Inactive)
s
0.1
0.0
F23 Starting frequency (Freq.)
F23
START Hz
0.1 to 60.0Hz
Hz
0.1
0.5
N
F24 (Holding time)
F24
HOLDING t
0.0 to 10.0s
s
0.1
0.0
F25 Stop frequency
F25
STOP Hz
0.1 to 60.0Hz
Hz
0.1
0.2
N
F26 Motor sound (Carrier freq.)
F26
MTR SOUND
0.75 to 15kHz (Vary by HP)
kHz
1
2
Y
F27 (Sound tone)
F27
SOUND TONE
0 to 3
-
-
0
F30 FMA (Voltage adjust)
F30
FMA V-ADJ
0 to 200%
%
1
100
Y
F31 (Function)
F31
FMA FUNC
0 to 11
-
-
0
F33 FMP (Pulse rate)
F33
FMP PULSES
300 to 6000p/s (full scale)
p/s
1
1440
Y
F34 (Voltage adjust)
F34
FMP V-ADJ
0%, 1 to 200%
%
1
0
F35 (Function)
F35
FMP FUNC
0 to 10
-
-
0
F36 30RY operation mode
F36
30RY MODE
0, 1
-
-
0
Y
F40 Torque limiter 1 (Driving)
F40
DRV TRQ 1
20 to 150%, 999
%
1
999
Y
F41 (Braking)
F41
BRK TRQ 1
0%, 20 to 150%, 999
999
F42 Torque vector control 1
F42
TRQVECTOR1
0, 1
-
-
0
N